RUGGEDCOM RSG2200
Installation Guide
1.
Remove the terminal block cover.
2.
If a screw-type terminal block is installed, remove the screws from the appropriate terminals. Use these
screws along with #6 ring lugs to secure the wires to the terminal block.
3.
Connect the positive wire from the power source to the positive terminal on the terminal block. For more
information, refer to
1
3
Figure 6: Terminal Block Wiring
1. Screw-Type Terminal Block
Ground Terminal
4.
Connect the negative wire from the power source to the negative terminal on the terminal block. For more
information, refer to
5.
Install the supplied metal jumper between terminals 2, 4 and 6 to connect the surge ground terminals to the
chassis ground terminal. The surge ground terminals are used as the ground conductor for all surge and
transient suppression circuitry internal to the unit.
6.
Connect the ground terminal on the power source to the chassis ground terminal on the device. For more
information, refer to
DANGER!
Electrocution hazard – risk of death, serious personal injury and/or damage to the device. Make
sure the supplied terminal block cover is always installed before the device is powered.
7.
Install the terminal block cover.
Section 2.2.3

Wiring Examples

The following illustrate how to connect power to single and dual power supplies.
Wiring Examples
Section 2.2.3, "Wiring
4
5
4
5
6
7
6
2. Pluggable Terminal Block
7. Chassis Ground Terminal
Section 2.2.3, "Wiring
Section 2.4, "Grounding the Device"
Examples".
4
3. Jumper
4. Positive Terminal
Examples".
6
7
6
5
4
5
3
5. Negative Terminal
Chapter 2
Installing Device
2
6. Surge
11

Advertisement

Table of Contents
loading