2.2.3 Wiring Examples - Siemens SIMATIC NET RUGGEDCOM RS1600 Installation Manual

Rugged ethernet switches
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RS1600:
Table of Contents

Advertisement

1.
Connect the positive wire from the power source to the positive/hot (+/H)
terminal on the terminal block. For more information, refer to
(Page
Figure 2.5
2.
Connect the negative wire from the power source to the negative/neutral (-/N)
terminal on the terminal block.
3.
Using a braided wire or other appropriate grounding wire, connect the surge
ground terminal to the chassis ground connection. The surge ground terminal
is used as the ground conductor for all surge and transient suppression circuitry
internal to the unit.
4.
Connect the ground terminal on the power source to the chassis ground
terminal on the device.
2.2.3
Wiring Examples
The following illustrate how to connect power to single and dual power supplies.
RUGGEDCOM RS1600
Installation Manual, 01/2021, C79000-G8976-1013-03
All manuals and user guides at all-guides.com
13)".
1
2
3
Positive/Hot (+/H) Terminal
1
Negative/Neutral (-/N) Terminal
2
Surge Ground Terminal
3
Chassis Ground Terminal
4
Terminal Block Wiring