Appendix One

Appendix One: Control Mode 02 Description

Overview

The functional differences described in this Appendix are available when Control Mode 02 is selected from the
start-up screens. Control Mode 02 assigns alternative functions to certain wiring Terminal Connections and
allows additional airflow settings to be accessed via the
control.

Terminal Connections and Functions

The following switching Functions are available with Control Mode 02:
Terminal No.
S/W1
S/W2
S/W3
S/W4
S/W5
P1 0-10V
P2 0-10V
LED
L
N
EARTH
LS
N.B If control mode 02 is selected then S/W5 must have a link connecting the + and – terminals or a
normally closed device such as a fire system.
Sentinel Kinetic MVHR Installation & Commissioning
Name
Switch 1
Switch 2
Switch 3
Switch 4
Switch 5
Proportional 1
Proportional 2
Red Light Emitting Diode
Output
Mains Live
Mains Neutral
Mains Earth
Switched Live
button on the front of the Kinetic unit or remote
Description (Control Mode 02)
With link fitted to J4 – Volt- free switch – Low Mode
With link fitted to J4 – Volt- free switch – Normal Mode
With link fitted to J4 – Volt- free switch – Boost Mode
Volt-free contact for sensor input between + and – terminals
(Momentary if SW/4 if SW4 Commissioning Screen set On)
With Vent-Wise PCB fitted to J4 - enables Vent-Wise momentary switch
input
Fire System or SW/5 open Stop
A 24 V DC sensor supply is output between the + and - terminals.
A 10 V proportional sensor input is received between S and - terminals
A 24 V DC sensor supply is output between the + and - terminals.
A 10 V proportional sensor input is received between S and - terminals
A 5 V LED driving signal output between the + and – terminals that
enables remote indication of a unit fault. See the Control Panel for fault
code (see Service/Fault Code Screens on page 44).
220-240 V AC, 50 Hz input
220-240 V AC, 50 Hz input
Earthing connector
220-240 V AC, 50 Hz input