Mitsubishi Electric FR-D720-070 Instruction Manual page 125

Table of Contents

Advertisement

Function assignment of external terminal and control
Setting
Signal
Function
Positive
Negative
logic
logic
90
190
Y90
Life alarm
Fault output 3
91
191
Y91
(power-off signal)
Current average value
93
193
Y93
monitor signal
Maintenance timer
95
195
Y95
signal
96
196
REM
Remote output
98
198
LF
Alarm output
99
199
ALM
Fault output
9999
No function
∗1
Note that when the frequency setting is varied using an analog signal or
alternate on and off depending on that varying speed and the timing of the varying speed due to acceleration/deceleration time setting.
(The output will not alternate on and off when the acceleration/deceleration time setting is "0s".)
REMARKS
The same function may be set to more than one terminal.
When the function is executed, the terminal conducts at the setting of any of "0 to 99", and does not conduct at the setting of
any of "100 to 199".
NOTE
Changing the terminal assignment using Pr.190, Pr.192 (output terminal function selection) may affect the other functions.
Make setting after confirming the function of each terminal.
Do not assign signals which repeat frequent ON/OFF to A, B, and C. Otherwise, the life of the relay contact decreases.
120
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Operation
Output when any of the control circuit capacitor, main
circuit capacitor and inrush current limit circuit or the
cooling fan approaches the end of its service life.
Output when a fault occurs due to the internal circuit failure
or the inverter wiring mistake, etc.
Average current value and maintenance timer value are
output as pulses.
The signal can not be set in Pr. 192 A,B,C terminal function
selection .
Output when Pr. 503 rises to or above the Pr. 504 setting.
Output to the terminal when a value is set to the parameter.
Output when an alarm (fan failure or communication error
warning) occurs.
Output when a fault occurs.
The signal output is stopped when the fault is reset.
of the operation panel, the output of the SU (up to frequency) signal may
Refer
Related
to
Parameter
Page
Pr. 255 to
229
Pr. 259
122
Pr. 555 to
234
Pr. 557
Pr. 503,
233
Pr. 504
Pr. 495, Pr.
126
496
Pr. 121,
183,
Pr. 244
228
122