Facing Requirements - Lopi 564 GSR2 25K CF Installation Manual

Deluxe fireplace
Table of Contents

Advertisement

Finalizing the Installation

Facing Requirements

The front of fireplace may be left uncovered (see "a" below).
Drywall (or other combustible) may be placed above, below, and to the sides of the fireplace (not over
the front of the fireplace (see "b" below).
Tile or other non-combustible facing may be placed along the front of the fireplace around the
perimeter of the glass opening (see "c" below). Typical installations use 12" (305mm) or greater of
non-combustible facing around the perimeter of the glass opening. Do not install facing over the
ledge to the glass opening.
WARNING: Do not use adhesive to secure the facing. The high temperatures of the
fireplace may cause adhesives to emit odors. Use mastic or thin set (or other non-
combustible, non-odorous adherent) to attach the facing.
NOTE: Screws may be used to secure cement board or tile backer to the fireplace. Do not
penetrate the fireplace more than 1/2" (13mm).
© Travis Industries
(for qualified installers only)
b
c
5/15/2019 - 1508
Drywall Support (3 total)
a
564 GSR2 25K CF (AUST)
33