Compressor Lock - Daikin RXL-W Series Service Manual

Inverter pair
Table of Contents

Advertisement

Troubleshooting for Outdoor Unit
7.5

Compressor Lock

E6
Error Code
Method of Error
A compressor lock is detected by the current waveform generated when applying high-frequency
Detection
voltage to the motor.
Error Decision
 If the error repeats, the system is shut down.
Conditions
 Reset condition: Continuous run for about 11 minutes without any other error
Supposed
 Closed stop valve
Causes
 Compressor locked
 Disconnection of compressor harness
Troubleshooting
Reference
Check No.12 Refer to P.189
Reference
Check No.15 Refer to P.193
163
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
(Precaution before turning on the power again)
Make sure the power has been off for at least 30 seconds.
Stop valve
closed?
NO
Turn off the power. Disconnect the
harnesses U, V, and W.
Check No.15
Check with the inverter analyzer.
Any LED off?
YES
Turn off the power and reconnect
the harnesses. Turn on the power
again and restart the system.
Emergency stop
without compressor running?
NO
System shut
down after errors repeated
several times?
YES
YES
∗ Inverter analyzer:
RSUK0917C
NO
YES
NO
SiUS092231E
Open the stop valve.
Correct the power supply or
replace the outdoor unit
PCB (main PCB).
Replace the compressor.
Check the electronic
expansion valve coil.
Go to Check No. 12.
Replace the compressor.
(R21067)
Part 6 Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents