Daikin RXL-W Series Service Manual page 155

Inverter pair
Table of Contents

Advertisement

SiUS092231E
Troubleshooting
Reference
Check No.11 Refer to P.189
Part 6 Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check the power supply voltage.
Is the
voltage fluctuation
within ±10% from the rated
value?
YES
Check the connection wires
between the indoor unit and the
outdoor unit.
Is there any wiring
error?
NO
Check the voltage of the
connection wires on the indoor
terminal block between No. 1
and No. 3, and between No. 2
and No. 3.
Properly
insulated?
YES
Check the LED A on the outdoor
unit PCB.
Is LED A
blinking?
Blink
Rotate the
outdoor fan manually.
Does the outdoor fan rotate
smoothly?
YES
Check No.11
Check the power supply
waveform.
Is there any
disturbance?
YES
NO
YES
NO
Continuously ON or OFF
NO
NO
Troubleshooting for FDMQ Series
Correct the power supply.
Correct the connection wires
between the indoor unit and
the outdoor unit.
Replace the connection wires
between the indoor unit and
outdoor unit.
Replace the outdoor unit PCB
(main PCB).
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Replace the indoor unit PCB
(control PCB).
Locate and eliminate the
cause of the disturbance of
the power supply waveform.
(R24622)
150

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents