Download Print this page

Trane TR200 Operating Instructions Manual page 9

Embedded bacnet
Hide thumbs Also See for TR200:

Advertisement

How to Install
The BACnet Interface
Cabling
Cable lengths and number of nodes
The maximum cable length allowable in one segment is dependent on the transmission speed. The total cable length
includes drop cables if any. A drop cable is the connection from the main bus cable to each node.
Drop cable connection (i.e. T-connection) is not recommended, due to the increased risk of reflection occurring. Instead,
Trane recommends direct connection of the frequency converter.
Note that a repeater is a node in both of the two segments it connects. The number of frequency converters is based on a
single
system. If there are two or more devices (e.g. PC tools, Routers), the number of frequency converters must be
reduced correspondingly.
Maximum length of an
-
Impedance: 100 to 130 Ohm
-
Resistance: <110 Ohm/km
-
Capacitance: <100 pF/m
-
Distributed capacitance between conductors and shield shall be less that 200 pF per meter
Cross section: 0.82 mm 2 conductor area, corresponding to AWG 18
-
Cable type: twisted in pairs, 1 x 2, or 2 x 2 wires
-
Screening: Copper-braided screen or braided screen and foil screen
-
Use of the same cable type throughout the entire segment is recommended to avoid impedance mismatch.
Network Connection
Connect the frequency converter to the RS-485 network as follows (see also diagram):
1.
Connect signal wires to terminal 68 (P+) and terminal 69 (N-) on the main control board of the frequency converter.
2.
Connect the cable screen as described under chapter Bus Cabling.
Note
Screened, twisted-pair cables are recommended in order to reduce noise between conductors.
8
TP segment: 1200 meters (4000 feet)
TR200 Embedded BACnet Operating Instructions

Advertisement

loading