Parameters
8-03 Control Timeout Time
Applica-
[1.0 - 18000.0 s]
tion de-
pend-
ent*
8-04 Control Timeout Function
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
[7]
Select setup 1
[8]
Select setup 2
[9]
Select setup 3
[10]
Select setup 4
[20]
N2 Override Release
26
Range:
Function:
Enter the maximum time expected to pass between the reception of two
consecutive telegrams. If this time is exceeded, it indicates that the serial
communication has stopped. The function selected in par. 8-04
Function
Control Time-out Function will then be carried out.
In BACnet the control timeout is only triggered if some specific objects are
written. The object list hold information on the objects that triggers the control
timeout:
Analog Outputs
Binary Outputs
AV0
AV1
AV2
AV4
BV1
BV2
BV3
BV4
BV5
Multistate Outputs
Option:
Function:
Select the time-out function. The time-out function is activated when the control
word fails to be updated within the time period specified in par. 8-03
Timeout
Time. Choice [20] only appears after setting the Metasys N2 protocol.
TR200 Embedded BACnet Operating Instructions
Control Timeout