Trane TR200 Operating Instructions Manual page 32

Embedded bacnet
Hide thumbs Also See for TR200:

Advertisement

8-70 BACnet Device Instance
0 - 4194302
1 *
[0 - 4194302 ]
8-72 TP Max Managers
Range:
0 - 127
127 *
[0 - 127 ]
8-73 TP Max Info Frames
1 - 65534
1*
[1 - 65534 ]
8-74 "I-Am" Service
Option:
[0] *
Send at power-up
[1]
Continuously
8-75 Initialization Password
Range:
[Size
0 - 0
related]
0 *
[0 - 0]
TR200 Embedded BACnet Operating Instructions
Range:
Function:
The Device Instance number must be unique for the complete BACnet, not
only for this MS/TP Branch.
Enter a unique ID number for the BACnet device.
Function:
Define the address of the MS/TP device which holds the highest address in this
network. Decreasing this value optimizes polling for the token.
Define the address of the MS/TP device which holds the highest address in this
network. Decreasing this value optimizes polling for the token.
Range:
Function:
Define how many info/data frames the device is allowed to send while holding
the token.
Define how many info/data frames the device is allowed to send while holding
the token.
Function:
Choose whether the device should send the "I-Am" service message only at power-
up or continuously with an interval of approx. 1 min.
Function:
Enter the password needed for execution of Drive Re-initialization from BACnet.
Enter the password needed for execution of Drive Re-initialization from BACnet.
Parameters
31