How to Control the Frequency Converter
ID
Object_Name
Default
Writeable
EEPROM
name
BV:0
Reserved for VFD profile
BV:1
RUN/STOP
X
Command
BV:2
REF 1 / REF 2
X
Select
BV:3
Fault Reset
X
Command
BV:4
RUN / STOP
X
Monitor
BV:5
OK / FAULT
X
Monitor
BV:6
HAND / AU-
X
TO Reference
BV:7–20
Reserved for VFD profile
BV:21
Warning
X
BV:22
Trip
X
BV:23
Triplock
–
BV:24
Coasting
–
BV:25
CW/CCW
–
BV:26
Jog
–
BV:27
Reset
–
BV:28
Reset KWh
–
Counter
BV:29
Reset Run-
–
ning Hours
Counter
BV:30
Reverse
–
BV:31
Speed = ref-
–
erence
BV:32
Bus control
–
BV:33
Running
X
BV:34
Ramp 1/
–
Ramp 2
BV:35
ECB Test
–
Mode
BV:36
ECB Drive
–
Mode
BV:37
ECB auto. By-
–
pass Enable
20
Present_Value
Param-
Bit number
Writeable
eter
X
CTW=047c +
6 reverse
Reversing bit
15
15
X
Note 1
n/a
X
CTW
7
X
STW
1
X
STW
3, 6, 7
X
16-95
1
X
STW
7
X
STW
3
–
STW
6
–
CTW
3
–
CTW
15
–
CTW
8
–
CTW
7
–
1506
n/a
–
1507
n/a
–
STW
1
–
STW
8
–
STW
9
X
STW
11
–
CTW
9
–
3110
0
–
3110
1
–
3110
2
Cmd.able
EEPROM
X
X
X
X
X
–
–
–
–
–
–
–
–
–
–
–
–
–
X
X
X
X
X
X
X
X
X
–
X
–
–
–
–
–
–
–
–
–
X
X
–
–
–
–
–
–
TR200 Embedded BACnet Operating Instructions
Time-
Op-
out
tion
–
X
–
X
X
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
X
–
–
X
–
–
X
–
–
X
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
–
MCO
104
–
–
MCO
104
–
–
MCO
104