Trane TR200 Operating Instructions Manual page 29

Embedded bacnet
Hide thumbs Also See for TR200:

Advertisement

Parameters
8-32 Baud Rate
Option:
[2]
9600 Baud
[3]
19200 Baud
[4] *
38400 Baud
[6]
76800 Baud
Default refers to the FC Protocol.
8-33 Parity / Stop Bits
Option:
[0] *
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
8-35 Minimum Response Delay
Range:
Applica-
[Application dependant]
tion de-
pend-
ent*
8-36 Maximum Response Delay
Range:
Applica-
[Application dependant]
tion de-
pend-
ent*
8-37 Maximum Inter-Char Delay
Range:
Applica-
[Application dependant]
tion de-
pend-
ent*
28
Function:
Baud rate selection depends on Protocol selection in par. 8-30 Protocol.
Function:
Parity and Stop Bits for the protocol par. 8-30
some of the protocols, not all options will be visible. Default depends on the
protocol selected.
Function:
Specify the minimum delay time between receiving a request and transmitting a
response. This is used for overcoming modem turnaround delays.
Function:
Specify the maximum permissible delay time between transmitting a request and
receiving a response. Exceeding this delay time will cause control word time-out.
Function:
Specify the maximum permissible time interval between receipt of two bytes.
This parameter activates time-out if transmission is interrupted.
TR200 Embedded BACnet Operating Instructions
Protocol
using the Drive Port. For