Binary Input- and Output Objects
ID
Object_Name
Default name
Parameter
BI:0
Digital input Term33
BI:1
Digital input Term32
BI:2
Digital input Term29
BI:3
Digital input Term27
BI:4
Digital input Term19
BI:5
Digital input Term18
BI:6
Digital input Term37
BI:7
Digital input GPIO Term X30/2
BI:8
Digital input GPIO Term X30/3
BI:9
Digital input GPIO Term X30/4
BI:10..BI:15 are reserved for P1660/x (MCB 115)
Table 5. 5: Binary inputs
ID
Object_Name
Default name
Parameter
BO:0
Digital Output Term 27
BO:1
Digital Output Term 29
BO:2
GPIO Output Term X30/6
BO:3
GPIO Output Term X30/7
BO:4
Relay 1
BO:5
Relay 2
BO:6
Option B Relay 1 Output
BO:7
Option B Relay 2 Output
BO:8
Option B Relay 3 Output
BO:9..BO:39 are reserved for Output P590/x (MCB 115)
Table 5. 6: Binary outputs
TR200 Embedded BACnet Operating Instructions
How to Control the Frequency Converter
Present_Value
Bit number
1660
1660
1660
1660
1660
1660
1660
1660
1660
1660
Present_Value
Unit
Writeable
Cmd.able
590
0
X
590
1
X
590
2
X
590
3
X
590
4
X
590
5
X
590
6
X
590
7
X
590
8
X
Option
1
2
3
4
5
6
9
MCB 101
8
MCB 101
7
MCB 101
Timeout
Option
X
X
X
X
X
X
MCB 101
X
X
MCB 101
X
X
X
X
X
X
MCB 105
X
X
MCB 105
X
X
MCB 105