How to Configure the System
Control Word Time-out Function
Par. 8-03
Control Timeout Time
option.
Example of a simple setup of BACnet
This example shows the necessary steps to set up the TR200 BACnet interface with the following system requirements:
TP running at 38,400 Baud
MAC address 20 for the TR200 on the MS/TP network
Device Instance number 1025 for the TR200
Highest number of a Manager device is 35
Start/stop of Drive from BACnet only
Reference from BACnet
Read status of Drive (Actual speed)
Set the following parameters:
Name
Protocol
Address
Drive Port Baud Rate
Coasting Select
BACnet device Instance
MS/TP Max Managers
After the parameters have been set according the table above, the drive has to be unpowered and repowered before the
changes take effect. When the frequency converter is detected by the BMS, the drive can be controlled by BV:1, which will start
the motor if set to [1]. Setting AV:1 will set the speed reference of the drive. The actual speed can be monitored via AV:3. See
also Analog Input and Output Objects section.
14
and par. 8-04
Control Timeout Function
are not enabled in this version of the BACnet
Par. number
8-30
8-31
8-32
8-50
8-70
8-72
TR200 Embedded BACnet Operating Instructions
Value
BACnet [5]
20
38,400 Baud [4]
Bus [1]
1025
35