4.3

Settings menu MU 100

The settings on the MU 100 can be performed via the control
unit. Depending on the software version, certain settings are
displayed.
Menu item
PM10 pump modulation
PM10 control type
PM10 voltage min. vol.
PM10 voltage max. vol.
Table 8
Menu MU 100 (for RC310 with NF18.xx)
Menu item
Pump config. (Boiler circulation pump PC0)
Output config.
Pump output 230V
Control mode, pump
( chapter 2, page 16)
Max. pump output
Min. pump output
Pump fault input
Pump overrun
Overrun time
Temp.dep. overrun
Set temperature differential
Pump control
Max. value
Max. flow temp
control
Maximum range
Proportional range
dT set value
Proportional factor
dT control
Integral factor
Differential factor
24
All manuals and user guides at all-guides.com
Settings/adjustment range
Yes | No
Output | 0.5 ... 2.5 ... 10 K
0 ... 10 V
0 ... 10 V
Settings/adjustment range
PWM | InversePWM | 0-10V
Permanent | Switched
Diff-T.Flow/Return boiler |
Burner output | Diff.-Flow-
T.Boiler-header
0 ... 100 %
0 ... 100 %
Close | Open
0 ... 3 ...60 min
on | off
2 ... 3 ... 10 K
85 ... 100 °C
1 ... 4 ... 20 K
1 ... 5 ... 20 K
off | 0.5 ... 2.5 ... 20 K
1 ... 10 ... 100 K
0 ... 60 ... 600 s
0 ... 150 s
The factory settings are depicted as highlighted in the
following table.
Remark/restriction
How is the pump to be modulated? (e.g.
wall-mounted indoor unit with internal
pump: inverted pulse width modulation,
floor-standing heat source with external
boiler circulation pump: 0-10 V)
Select supply voltage for pump
Select pump control mode
Set maximum output signal for pump
Set minimum output signal for pump
Fault signal when opening or closing the
contacts?
Set the pump overrun time
Switch on temperature-dependent pump
overrun
Enter set temperature differential for end
of overrun
Enter maximum flow temperature
Enter width of max. range
Enter width of proportional range
Enter temperature differential set value
Set proportional factor for controller
Set integral factor for control unit
Set differential factor for control unit
Remark/restriction
Selection of output control or
temperature control.