Process Error Messages - Endress+Hauser Proline Promass 83 Operating Instructions Manual

Coriolis mass flow measuring system
Hide thumbs Also See for Proline Promass 83:
Table of Contents

Advertisement

Proline Promass 83 MODBUS RS485
!
MODBUS
Register:
Register:
6859
6821
Data type:
Data type:
Integer
String (18 byte)
Response to a fault message:
The value "NaN" (not a number) is
transmitted to the MODBUS master
instead of the current measured
value.
1
SYSTEM OK
126
> BATCH TIME
Endress+Hauser
9.3

Process error messages

Note!
See the information on → Page 39
No.
Device status message
(local display)
Depicted on the local display:
S = System error
$ = Fault message (with an effect on the outputs)
! = Notice message (without any effect on the outputs)
There is no error present in the device
471 P: > BATCH TIME
$: # 471
Cause
Remedy / spare part
The maximum permitted
1. Increase flow rate
batching time was exceeded.
2. Check valve (opening
3. Adjust time setting to changed batch quantity
!
If the errors listed above occur, these are displayed in
the Home position flashing continuously.
• General:
• Batching via status input:
• Batching via operating keys (soft keys)
• Batching via the BATCHING PROCESS function
• Batching via MODBUS:
Troubleshooting
Note!
These error messages can be reset by configuring
any batching parameter. It is sufficient to confirm
with the OS key and then the F key.
The error message can be reset by means of a pulse.
Another pulse then restarts the batching.
The error message is reset by pressing the START
key. Pressing the START key a second time starts
the batching process.
(7260):
The error message can be reset by pressing the
STOP, START, HOLD or GO ON keys. Pressing the
START key a second time starts the batching
process.
The error message can be reset via MODBUS by
selecting 4 = RESET in the "BATCH PROCEDURE
(7260)" parameter.
93