DANIEL 1500 Series User Manual page 45

Liquid turbine meter
Hide thumbs Also See for 1500 Series:
Table of Contents

Advertisement

Operating conditions and specifications
March 2019
Table 2-5: 1815B Zero crossing preamplifier performance
Parameter type
Outputs
Construction
Table 2-6: 1817X Bi-directional preamplifier performance
Parameter type
Inputs
Outputs
Construction
Wiring and cable connections
The pickoff input signal connections are made at terminal strip connection TB2 for
Channel A, and TB3 for Channel B. Power supply and output signal connections are made
at terminal strip TB1. Refer to
Important
For single channel wiring use multi-conductor control and instrumentation cable
(18AWG), or equivalent.
Earth ground shield at one end only.
Insulate the shield at the other end.
For dual channel wiring use multi-conductor control and instrumentation cable
(18AWG), or equivalent.
Connect both shields to earth ground at one end of the cables and insulate the shields
at the other end.
The LME housing should be at earth ground.
48
Description
Powered pulse output:
Type: Square wave
Frequency range: ≤ 5 kHz
Amplitude: 0-12 V
Delrin housing
Solid epoxy encapsulation
Description
Supply voltage: 11.5-36 VDC
Sensor type: Reluctance
Signal: Sine wave
Preamplifier sensitivity: 40 mVpp
Temperature range: -40 ºC to 85 ºC (-40 ºF to 185 ºF)
Powered pulse output:
Type: Square wave
Frequency range: ≤ 5 kHz
Amplitude: 0-Vs
Delrin housing
Solid epoxy encapsulation
Table
2-7,
Table
2-8,
Table 2-9
Daniel Series 1500 Liquid Turbine Meter, NPS 3-24
User manual
USER MANUAL
P/N 3-9008-515
(continued)
and
Table
2-10.
www.Daniel.com
45

Advertisement

Table of Contents
loading

Related Products for DANIEL 1500 Series

Table of Contents