Assa Abloy Corbin Russwin PED5000 Series Installation Instructions Manual page 24

Exit devices
Hide thumbs Also See for Corbin Russwin PED5000 Series:
Table of Contents

Advertisement

PED4000/PED5000 Series Exit Devices
with optional connections
Installation Manual
13
Appendix A: Harness Wiring Reconfiguration, continued
Follow correct Horizontal Insertion view when inserting crimped terminal/wire into socket
(26-pin connector), as shown below. For re-pinning, please contact technical service at 1-800-727-5477.
See page 23 for wire table .
If the M93 NC (22-2) contact is required instead of M93 NO (22-4, Tan wire):
Remove crimped contact/tan wire assembly from 22 pin connector
position 4 (22-4), using pointed tool to lift up plastic locking housing
lance on connector, then slowly and carefully remove the contact/tan
wire assembly from connector by hand.
Insert crimped contact/wire assembly into new connector position 22-2 (M93 NC).
Be sure to follow correct Horizontal Insertion view when inserting crimped terminal/wire
into socket (22-pin connector), as shown.
Plug in 22-pin mating harness connectors, re-install rail metal insert cover, complete hinge
side facility wiring, then re-install end cap.
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in
part without the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
Housing lance
Pin 1
Crimp socket
Pin 2
contact
Pin 21
Pin 22
Contact lance
Do not tilt crimped terminals during insertion .
24
FM575 01/23