PED4000/PED5000 Series Exit Devices
with optional connections
Installation Manual
11
M93, 910/A, 930/A, 903/A, 905/A (Electromechanical Exit Trim), continued
120VAC (L,N,G)
To closed Fire
Alarm Contact
Contact opens, disconnects 24VDC
from Electromechanical Exit Trim
m
ElectroLynx Field
Wiring Term
(12 wires max)
QC12 Hinge Pigtail
or
15' Frame Harness
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2023 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole or in
part without the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
(-)
Securitron
+24VDC
BPS
24VDC
1AMP
Power Supply
QC12 Hinge
Exit Rail Assembly
Door Harness
3" Typical
Pluggable 8-pin & 4-pin
connectors
C
NC
Wire M93 switch (COM & NO) contacts
Outside Card
to monitor device, as required.
Reader Relay,
Note: If M93 NC contact is required,
or other switch
(by others)
Electromechanical Exit Trim (ET) wiring:
Fail Safe Wiring (use C, NC contacts)
C
NO
Fail Secure Wiring (C, NO contacts)
Note: The Electromechanical ET
mounts on other side of door
behind the chassis (ET not shown)
3-pin
connector
5, Green (M93 NC )
4, Yellow (M93 NO)
3, Orange (M93 COM)
2, Red (ET+)
1, Black, (ET-)
2-pin
connector
Electromechanical Exit Trim (ET) with M93
Trim Lever Monitor switch
M93 910/A, 903/A Fail Safe
M93 930/A, 905/A Fail Safe
M93 Switch Rating: 1A max @ 30VDC
*
Note: The Electromechanical ET has a wire that
ring that is connected to black ET- wire.
22
QC12 Hinge Pigtail or
15' Frame Harness
Pink
(M93
4, Tan
(M93 NO)
4-pin connector
n
FM575 01/23
Connect
to QC12
Hinge 4-pin
connector