VIPA HMI
Selection menu
Settings
Info/Update (firmware)
Autostart
HB160 | TP-ECO | 62H-MHC0 | en | 17-01
A delay time of 5 seconds is default. In the selection menu under "Autostart" you can
adjust this time.
There are following buttons in the selection menu:
n
Settings
n
Info/Update
n
Autostart
n
Backup
n
Exit
n
Back
In [Settings] under Change Settings you can set a password for the Startup-Manager.
The password will be requested when interrupting the start countdown or before closing
the Startup-Managers by "Exit". By default, no password is defined. In Control Panel
[Open...] the system settings like brightness of the display can be preset or the display
can be re-calibrated. Here the MPI/DP slave interface may also be configured. Further
you get here the Touch Panel information: product number, serial number and licenses.
To execute the firmware update press the button [Info/Update]. After clicking on [Info/
Update] the current image is displayed under "image version" with panel name, creation
date and version number.
With [Make Screen Shot] you can make a screen shot of the panel information and select
a destination for its storage.
With [Search Image] a list of all the firmware images is shown, which are available on the
panel and connected storage media. These images will be listed with create data and
version number. Choose your new image.
If the select image is not suited for your panel, an error massage appears. If the image is
suited for your panel, in the following message the current installed image version and
the new selected image version are listed.
1.
Click on [Make Image Update] to execute the update. This can take a few seconds.
2.
In the following window click on [Finish] to end the update.
ð Then the display gets dark.
3.
Switch the power supply off the panel off and on.
ð After the restart the calibration window is opened.
4.
Re-calibrate the panel as described. After calibration tap anywhere on the screen.
ð The calibration window will be closed.
5.
Via 'Start è Settings è Control Panel' start the program AutoRunMaker.
Ä Chapter 4.4 'Installation Movicon and Startup-Manager' on page 53
With [Autostart] you define which runtime and which project will be started automatically
together with the panel startup.
Deployment under Windows CE 6.0 Prof.
Commissioning > VIPA Startup-Manager