General data
EMC
Emitted interference
Noise immunity
zone B
*) Due to the high-energetic single pulses with Surge an appropriate external protective circuit with lightning protection elements like conductors for lightning and overvoltage is
necessary.
18
Standard
EN 61000-6-4
EN 61000-6-2
EN 61000-4-2
EN 61000-4-3
EN 61000-4-6
EN 61000-4-4
EN 61000-4-5
Comment
Class A (Industrial area)
Industrial area
ESD
8kV at air discharge (degree of severity 3),
4kV at contact discharge (degree of severity 2)
HF field immunity (casing)
80MHz ... 1000MHz, 10V/m, 80% AM (1kHz)
1.4GHz ... 2.0GHz, 3V/m, 80% AM (1kHz)
2GHz ... 2.7GHz, 1V/m, 80% AM (1kHz)
HF conducted
150kHz ... 80MHz, 10V, 80% AM (1kHz)
Burst, degree of severity 3
Surge, degree of severity 3 *
HB160 | TP-ECO | 62H-MHC0 | en | 17-01