Conformity is indicated by the CE marking affixed to the product. Conformity Information For more information regarding CE marking and Declaration of Con- formity (DoC), please contact your local VIPA customer service organization. HB160 | TP | 62M-JID0 | GB | 15-36...
VIPA GmbH, Ohmstraße 4, 91074 Herzogenaurach, Germany Tel.: +49 9132 744-1150 (Hotline) EMail: support@vipa.de 1.2 About this manual Objective and contents This manual describes the Touch Panel 62M-JID0-... from VIPA. It contains a description of the structure, project engineering and deployment. Product Order number...
This device is not certified for applications in – in explosive environments (EX-zone) Documentation The manual must be available to all personnel in the project design department installation department commissioning operation HB160 | TP | 62M-JID0 | GB | 15-36...
Page 7
– The national rules and regulations of the respective country must be satisfied (installation, safety, EMC ...) Disposal National rules and regulations apply to the disposal of the unit! HB160 | TP | 62M-JID0 | GB | 15-36...
Instruments must be grounded. Modifying electrostatic sensitive modules you should only use sol- dering irons with grounded tips. CAUTION! Personnel and instruments should be grounded when working on electrostatic sensitive modules. HB160 | TP | 62M-JID0 | GB | 15-36...
4 2x "Host"-USB-A interfaces 5 "Slave"-USB-B interface 6 RJ45 jack for Ethernet communication 7 RJ45 jack for Ethernet communication 8 Slot for DC 24V voltage supply 9 Slot for CF/SD/MMC storage medium HB160 | TP | 62M-JID0 | GB | 15-36...
Serial bus connection in 4-wire technology using full duplex mode Data communications up to a max. distance of 500m Data communication rate up to 115.2kBaud Serial bus connection in 2-wire technology using half duplex mode HB160 | TP | 62M-JID0 | GB | 15-36...
Page 12
The USB-A interface of your PC can be connected to the "Slave"- USB-B interface of your Touch Panel deploying the USB program- ming cable. The USB programming cable is delivered by VIPA with order No. 670-0KB10. HB160 | TP | 62M-JID0 | GB | 15-36...
The card may be plugged and removed during runtime and is immedi- ately listed as SDMMC Card at My Device. Please take care to plug the according card as shown on the back of the Touch Panel. HB160 | TP | 62M-JID0 | GB | 15-36...
Installation cutting (W x H) 311 x 249mm Front panel (W x H) 325 x 263mm Rear panel (W x H x D) 309 x 247 x 45mm Installation depth 45mm HB160 | TP | 62M-JID0 | GB | 15-36...
Page 15
– The deviation from the plane for the panel cut-out is 0.5mm. This condition must be fulfilled for the mounted HMI device. – Permissible surface roughness in the area of the seal: £ 120µm (friction coefficient 120) HB160 | TP | 62M-JID0 | GB | 15-36...
Display size (height) 184.5 mm Resolution 768 x 1024 / 1024 x 768 Aspect ratio Type of display TFT color (16.7M colors) MTBF Backlights (25°C) 50000 h System properties Processor Xscale 1.1 GHz HB160 | TP | 62M-JID0 | GB | 15-36...
Page 18
Number of USB-A interfaces USB-A connector USB-A (host) Number of USB-B interfaces USB-B connector USB-B (device) Number of ethernet interfaces Ethernet Ethernet 10/100 MBit Ethernet connector RJ45 Integrated ethernet switch ü Video connectors HB160 | TP | 62M-JID0 | GB | 15-36...
Page 19
1.5 mm Maximum front panel thickness 6 mm Weight 3674 g Environmental conditions Operating temperature 0 °C to 50 °C Storage temperature -20 °C to 60 °C Certifications UL certification in preparation HB160 | TP | 62M-JID0 | GB | 15-36...
10 s Operating controls Touchscreen resistive Touch function Single Touch Keyboard external via USB Mouse external via USB Interfaces MPI, PROFIBUS-DP RS485 isolated MPI, PROFIBUS-DP connector Sub-D, 9-pin, female Serial, COM1 RS232 HB160 | TP | 62M-JID0 | GB | 15-36...
Page 21
IP 20 Dimensions Front panel 325 mm x 263 mm x 7.5 mm Rear panel 309 mm x 247 mm x 45 mm Installation cut-out Width 311 mm Height 249 mm HB160 | TP | 62M-JID0 | GB | 15-36...
Page 22
1.5 mm Maximum front panel thickness 6 mm Weight 3674 g Environmental conditions Operating temperature 0 °C to 50 °C Storage temperature -20 °C to 60 °C Certifications UL certification in preparation HB160 | TP | 62M-JID0 | GB | 15-36...
Now bolt the lever [5] clockwise with the screwdriver [4] until it rotates to the outside. Further screwing bolts the lever to the front panel until it holds this to the control cabinet front. HB160 | TP | 62M-JID0 | GB | 15-36...
Page 24
Insert the insulation-stripped wire into the round opening. You can use wires with a cross-section from 0.08mm to 2.5mm By removing the screwdriver the wire is connected safely with the plug connector via a spring. HB160 | TP | 62M-JID0 | GB | 15-36...
A delay time of 5 seconds is default. In the selection menu under "Autostart" you can adjust this time. Selection menu There are following buttons in the selection menu: Settings Info/Update Autostart HB160 | TP | 62M-JID0 | GB | 15-36...
Page 26
To remain the settings permanently, they have to be saved with KuK Tools [Store]. Autostart With [Autostart] you define which runtime and which project will be started automatically together with the panel startup. HB160 | TP | 62M-JID0 | GB | 15-36...
Page 27
Via "Rotation" the orientation of the panel can be changed. Via "Program start" with [+] you can add programmes, which have to start automatically. Select "start" and assign a name for the program. HB160 | TP | 62M-JID0 | GB | 15-36...
Page 28
The VIPA Startup-Manager will be closed by [Exit] and the system Ò returns to the Windows screen. Back With [Back] you get back to the start screen of the VIPA Startup-Man- ager. HB160 | TP | 62M-JID0 | GB | 15-36...
CE is a 32bit, open and scalable platform for a multiplicity of communication and data processing devices. The func- tions like multi-tasking and multi-threading are supported by this oper- ating system. HB160 | TP | 62M-JID0 | GB | 15-36...
Page 30
Please consider that changes which are made are set back after PowerOFF-PowerON and are only stored via [Store] which can be found under ‘Start è Programs è KuK_Tools è KuK Tools’. HB160 | TP | 62M-JID0 | GB | 15-36...
Ethernet, the symbol is displayed crossed out. Keyboard layout If you’ve connected a keyboard you can choose the requested language layout via this button. Time This area shows the time that you can change via double click. HB160 | TP | 62M-JID0 | GB | 15-36...
Page 32
At the moment the following standard keyboards are imple- mented: Keyboard At pushed Shift key: At pushed [a´ü] key: Please note that äöü can exclusively be entered via the software keyboard "Keyboard". HB160 | TP | 62M-JID0 | GB | 15-36...
Page 33
The software keyboard allows you to enter key entries without con- necting an external keyboard. As soon as an entry is required the software keyboard is automatically shown. Hide Input Panel hides the keyboard again. HB160 | TP | 62M-JID0 | GB | 15-36...
Page 34
Here you set the highest MPI address (highest station address). Within a MPI network the highest MPI address must be identical! With TS (this station) you set the local MPI address for the Touch Panel. HB160 | TP | 62M-JID0 | GB | 15-36...
Installation Download the ActiveSync from the Microsoft website and start the file MSASYNC.EXE. Start the installation with [Next]. Choose an installation directory and click on [Next]. ð ActiveSync is installed. HB160 | TP | 62M-JID0 | GB | 15-36...
Page 36
PC and turn on the Touch Panel. ð The USB device (Touch Panel) is recognized and the dialog window "new partnership" opens. Choose "yes" for fixing a partnership and push [Next]. HB160 | TP | 62M-JID0 | GB | 15-36...
Password: vipatp Overview Per default the following server are integrated: ftp server (activated) http server (activated) Telnet (activated) VNC (not activated) Phrases Phrases that are used in the description of the server: HB160 | TP | 62M-JID0 | GB | 15-36...
PC with Windows Explorer as ftp client and your Touch Panel. Connect your Touch Panel with the network where your PC is a member via an Ethernet cable. Switch on your Touch Panel. HB160 | TP | 62M-JID0 | GB | 15-36...
The login as web admin requires the following steps: Start the web browser at your PC and enter the following into the address bar: IP address/webadmin Enter the following into the authentification: User name: wince Password: vipatp HB160 | TP | 62M-JID0 | GB | 15-36...
After establishment of a Telnet connection the Panel PC provides you with commands. A list of possible commands with a short description is available via the command help. By beginning with "help" before a command you receive help to this command. HB160 | TP | 62M-JID0 | GB | 15-36...
You may also start the VNC server at the Touch Panel via a Telnet connection by entering the command winvnc in the command console with an active Telnet connection. Now start the VNC client vncviewer.exe on your PC. HB160 | TP | 62M-JID0 | GB | 15-36...
The access to the network resource is performed with the commands Net view and Net use. List released resources Shared resources of a network PC can be listed by the command: \> net view PC-Name HB160 | TP | 62M-JID0 | GB | 15-36...
Page 43
Successfully mapped to network printer The printer can now be accessed as "network\printer". Test print For example you can print the content of the current directory using \> dir > network\printer. HB160 | TP | 62M-JID0 | GB | 15-36...
Page 44
"archive" of "test server". To save the settings also after power on, you have to store them to the registry with ‘START è Programs è KuK_Tools è KuK Tools’ [Store]. HB160 | TP | 62M-JID0 | GB | 15-36...
Depending on the spreading medium (lead bound or lead free) and the distance to the interference cause, interferences to your control occur by means of different coupling mechanisms. There are: galvanic coupling capacitive coupling inductive coupling radiant coupling HB160 | TP | 62M-JID0 | GB | 15-36...
Page 46
(e.g. walkie-talkie) wave meets a line circuit. The Sparking lines (sparking hit of the wave inducts currents plugs, collector of electric and voltages. motors, welding devices) HB160 | TP | 62M-JID0 | GB | 15-36...
A correctly done grounding sup- inactive metal parts ports an unambiguous reference potential for the control and reduces the impact of coupled interferences. HB160 | TP | 62M-JID0 | GB | 15-36...
>400V Group D Lines for H1 respectively TCP/IP Combination of groups Following the table you may see the conditions for the cabling of the line groups by combining the single groups: HB160 | TP | 62M-JID0 | GB | 15-36...
Page 49
– Install these protective elements at the location where the cables enter the building. Any lightning protection system must be based on an indi- vidual assessment of the entire plant. For questions please contact VIPA GmbH. HB160 | TP | 62M-JID0 | GB | 15-36...
Page 50
The one-sided grounding of screens may provide advantages when: It is not possible to install an equipotential bonding conductor Analogue signals (a few mV or mA) must be transmitted Foil-type screening (static screening) is employed. HB160 | TP | 62M-JID0 | GB | 15-36...
(e.g. relay contacts). In this case the integrated suppressors on the module are also disabled. You can connect diodes to suppress back-emc, varis- tors or RC-networks to the inductors. HB160 | TP | 62M-JID0 | GB | 15-36...
Page 52
Suppression of fluores- cent lamps in cubicles 1 Fluorescent lamp 2 Screen above the lamp 3 Screened cable 4 Switch with metallic cover 5 Line filter or screened power cable HB160 | TP | 62M-JID0 | GB | 15-36...
Have the screens been connected by means of large-surface and low- impedance cable clamps? Cable screens grounded both-sided where possible? Inductors Have the coils of contactors controlled by means of contacts been connected to snubber networks? HB160 | TP | 62M-JID0 | GB | 15-36...