Table of Contents

Advertisement

3. Verify that the status LED on the corresponding GFCI
receptacle (Figure 93) is ON (GREEN).
GREEN
STATUS
LED (ON)
Figure 93. GFCI Receptacle (ON)
4. Press the TEST button (Figure 94) on the GFCI
receptacle and verify that the status LED turns OFF.
STATUS
LED (OFF)
Figure 94. GFCI Receptacle (OFF)
5. Press the RESET button (Figure 95) to restore power
to the GFCI receptacle and verify that the status LED
is ON (GREEN).
GREEN
STATUS
LED (ON)
Figure 95. GFCI Receptacle (ON/Restore)
6. If the status LED (Figure 96) is flashing (RED),
DO NOT use the GFCI receptacle and replace it
immediately.
RED
STATUS LED
(FLASHING)
Figure 96. GFCI Receptacle (Red Flashing LED)
DCA600SSV4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #2 (11/15/22) — PAGE 57
TEST
BUTTON
RESET
BUTTON
7. Repeat the above procedure for all other GFCI
receptacles.
GENERATOR STORAGE
For long-term storage of the generator the following is
recommended:
„ Drain the fuel tank completely. Treat with a fuel stabilizer
if necessary.
„ Completely drain the oil from the crankcase and refill if
necessary with fresh oil.
„ Clean the entire generator, internal and external.
„ Cover the generator and store in a clean, dry place.
„ Disconnect the battery.
„ Make sure engine coolant is at the proper level.
„ If the generator is mounted on a trailer, jack the trailer
up and place it on blocks so the tires do not touch the
ground, or block and completely remove the tires.
MAINTENANCE