PowerBalance™ (Figure 16) is an optional load
management solution that helps protect the engine generator
from problems resulting from sustained low-load operations
(defined as less than 30% of the generator full-load rating).

POWERBALANCE™

ASSEMBLY
„ The load management controller senses and increases
engine load automatically using resistive coils when the
controller determines that the temperature and/or load
is too low.
DCA600SSV4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #2 (11/15/22) — PAGE 31
„ PowerBalance™ continuously monitors engine load by
sensing the engine exhaust temperature.
Figure 16. PowerBalance™
„ When additional load demands are placed on
the generator that bring it to an optimum level,
PowerBalance™ will automatically deactivate this
additional load and remain ready for reactivation should
exhaust temperatures drop.