Generator Startup Procedure (Manual) - MQ Power WHISPERWATT DCA600SSV4F3 Operation Manual

60hz generator (volvo penta twd1672ge diesel engine)
Table of Contents

Advertisement

BEFORE STARTING
CAUTION
The engine's exhaust contains harmful emissions.
ALWAYS have adequate ventilation when operating.
Direct exhaust away from nearby personnel.
WARNING
NEVER manually start the engine with the main or
auxiliary circuit breakers in the ON (closed) position.
1. If applicable, perform the following:
• To ensure good starting, apply commercial power to
the internal battery charger receptacle via commercial
power. An external power cord will be required. This
capability is an option.
• In cold weather conditions, apply commercial power
to the engine block heater receptacle via commercial
power. An external power cord will be required. This
capability is an option.
2. Press the Main Circuit Breaker OFF switch (Figure 49).
Figure 49. Main Circuit Breaker OFF Switch
3. Verify that the Main Circuit Breaker OFF lamp
(Figure 50) is lit (ON).
Figure 50. Main Circuit Breaker OFF Lamp
4. Place the GFCI circuit breakers (Figure 51) in the OFF
position.
DCA600SSV4F3 60 HZ GENERATOR • OPERATION MANUAL — REV. #2 (11/15/22) — PAGE 43

GENERATOR STARTUP PROCEDURE (MANUAL)

OFF
OFF
Figure 51. GFCI Circuit Breakers (Off)
5. Connect the load to the UVWO terminals or auxiliary
receptacles as shown in Figure 52. These load
connection points can be found on the output terminal
panel. To access the UVWO busbar terminals or other
power receptacles, unlock the access cover and lift
the door.
GFCI
RECEPTACLES
LOAD
VOLTAGE
OUTPUT
TERMINALS
W
V
U
R E
D
B L
A C
K
Figure 52. Load Connections
6. Tighten the UVWO terminal nuts securely to prevent
load wires from slipping out.
N
G R E E
G R
O U
D .
G N
O
W H
I T E
B L
U E
N E
U T
R A
L
L O
A D
N D