18.3 Fault messages
The tables below show potential faults and
their causes.
Column 3 "Ackn." states whether the fault has
to be acknowledged after rectification or not.
M: Fault rectification must be acknowledged
manually. Only then is the ventilation unit
operable again.
A: Rectification of a temperature sensor
fault is detected by the control. Once rectified,
the ventilation unit continues running auto-
matically.
Collective alarm: A collective alarm is also
issued with every fault message. The collec-
tive alarm can be used via the potential-free
switching contact on the main board and, in
case of malfunction, switch on a signal lamp,
for example.
64
Fault /
Message
Failure of
Possible cause
Supply air
Supply air fan fault
fan
Break in a cable,
fan defective
Exhaust air
Exhaust air fan
fan
fault
Break in a cable,
fan defective
Communication
Communication
with main
with
control unit
main control unit
(comfort control
fault
unit)
Break in a cable;
main control unit
defective; wiring
incorrect
Sensor
Temperature
T-outside air,
sensor, upstream
upstream of
of EHE, fault
EHE
Break in a cable;
temperature
outside measuring
range
Unit
Unit inlet tempera-
T-air inlet
ture sensor fault
sensor
Break in a cable;
temperature outside
measuring range
Sensor
Outgoing air tem-
T-outgoing air
perature sensor
fault
Break in a cable;
temperature outside
measuring range
Sensor
Supply air temper-
T-supply air
ature sensor fault
Break in a cable;
temperature outside
measuring range
Sensor
External room
T-room external
temp. sensor fault
Break in a cable;
temperature outside
measuring range
Ackn.
M
M
A
A
A
A
A
A