MM DD YYYY HH:MM:SS.hh KYWD MESSAGE <CR> <LF>
Where
Equals
MM
Month (2 digits)
DD
Day (2 digits)
YYYY
Year (4 digits)
HH
Hour (2 digits)
MM
Minute (2 digits)
SS
Second (2 digits)
hh
Hundredths of Second (2 sdigits)
KYDW
Keyword (ALARM, NOTICE, COMMAND, or STATUS)
Message
System Diagnostic Information
<CR>
Carriage Return Character (ASCII 13)
<LF>
Line Feed (ASCII 10)
An alarm message is prefixed by the word "CLEAR" whenever an alarm is entered into the
Event History Log with a cleared status.
If a port is operating in Terminal mode and is connected to a computer, you can press [Esc] [H]
to print the entire log with a firmware version header. The log in terminal mode is always in
english.
MODEL: POWERWARE 9395E
CTO: TF12710000000
SERIAL:
MCU DSP:
MCU BOOTLOADER:
MCU PLD:
PMF 1 DSP:
PMF 1 BOOTLOADER:
PMF 1 PLD:
XSLOT CAN BRIDGE:
CSB DSP:
CSB BOOTLOADER:
DISPLAY:
TIME: 19:17:16 DATE: 03/23/2099
03/16/2099 21:25:20.355 S138: CONTROL POWER ON (PM1)
03/16/2099 21:25:20.515 N011: OUTPUT UNDER OR OVER FREQ (PM1)
03/16/2099 21:25:20.675 S302: EEPS CONFIGURING (PM1)
03/16/2099 21:25:23.475 N267: POWER MODULE CABLE FAIL 15 (PM1)
03/16/2099 21:25:25.180 N271: DC HW AMPS LIMIT (PM1)
03/16/2099 21:25:25.215 N007: INPUT AC UNDER VOLTAGE (PM1)
03/16/2099 21:25:25.850 N011: OUTPUT UNDER OR OVER FREQ OK (PM1)
...
03/23/2099 18:59:20.450 A199: BATTERIES DISCONNECTED (PM1)
ACTIVE ALARMS:
11 NOTICE: OUTPUT UNDER OR OVER FREQ (PM1)
12 ALARM: REMOTE EMERGENCY POWER OFF (MCU)
102 NOTICE: INVERTER L1 CURRENT LIMIT (PM1)
103 NOTICE: INVERTER L2 CURRENT LIMIT (PM1)
104 NOTICE: INVERTER L3 CURRENT LIMIT (PM1)
Figure 7-3. Sample Event History Log
69
70.81.14
80.40
1.00
80.81.14
80.40
1.00
0.00
70.81.14
1.12
1.06
UPS 200 kVA
User's and Installation Guide