NOTE If the load requires a neutral, a bypass source neutral must be provided. If the load does not require a neutral and
there is no neutral conductor connected at the bypass input, a neutral to ground bonding jumper must be installed. DO
NOT install both a source neutral and a bonding jumper.
Figure 4-5. Powerware 9395E 200 kVA UPS system, 400 V input and 400 V output dual-feed
46
UPS 200 kVA
User's and Installation Guide