Figure 3-8. Interface terminal detail AA
NOTE All building alarm inputs require an isolated normally-open or normally-closed contact or switch (rated at 24 Vdc,
20 mA minimum) connected between the alarm input and common terminal as shown. Building alarm inputs can be
programmed for use with either normally-open or normally-closed contacts. All control wiring and relay and switch
contacts are customer-supplied.
NOTE The building alarms can be programmed to display the alarm functional name.
NOTE A jumper wire must be connected between pins 1 and 2 on TB1, if the normally-closed Remote EPO contact is not used.
Figure 3-9. Terminal blocks TB1, TB2, TB3 and TB4 connector assignments
33