Table 2-1. UPS cabinet weights
The UPS cabinets use forced air cooling to regulate internal component temperature. Air inlets
are in the front of the cabinet and outlets are in the top. You must allow clearance in front of and
above each cabinet for proper air circulation. The clearances required around the UPS cabinet
are shown in Table 2-2.
From top of cabinet
From front of cabinet
From back of cabinet
From right side of cabinet
From left side of cabinet
Table 2-2. UPS cabinet clearances
The basic environmental requirements for operation of the UPS system are:
Ambient Temperature Range: 0-40°C
Recommended Operating Range: 20-25°C
Maximum Relative Humidity: 95%, noncondensing
The UPS ventilation requirements are shown in Table 2-3.
Rating/kVA
200 kVA
Table 2-3. Air conditioning or ventilation requirements during full load operation
Ventilation required for cooling air exhaust: approximately 1410 liter/sec /200kVA unit.
Shipping
930
Minimum clearance over the UPS cabinet is 458 mm for ventilation
915 mm working space
None required, but for easier service 500 mm is recommended.
100mm
None required
Input/output voltage
400/400
UPS 200 kVA
User's and Installation Guide
Weight kg
Installed
810
Heat rejection
BTU/hr x 1000/hr (kg-cal/hr)
39.67