PSEN sl-1.0p 1.1/1.1 VA

Function description

There is a high signal at safety outputs 12 and 22 if the following occur simultaneously:
The actuator is within the response range (safety gate closed) and
}
There is a high signal at the inputs S11 and S21 and
}
There is a high signal at the input S31 (control command for magnetic guard locking)
}
and
The holding force of the locking magnet has been tested successfully.
}
There is a low signal at safety outputs 12 and 22 if at least one of the following conditions
are met:
The actuator is outside the response range or
}
There is a low signal at the inputs S11 or S21 or
}
There is a low signal at the input S31 (control command for magnetic guard locking) or
}
The holding force of the locking magnet has not been tested successfully.
}
Signal output Y32
There is a high signal at the signal output Y32 if the actuator is within the response range
(safety gate closed).
Feasibility monitoring for safety inputs S11 and S21
If the signal at a safety input switches from high to low, while the other safety input re-
}
mains high, an unequal status is displayed:
Operating Manual PSEN sl-1.0p 1.1/1.1 VA
1003821-EN-12
U
B
A1
A2
Power supply
Power/Fault
S11
&
Input
S21
S31
Safety Gate
Receiver
Actuator
&
&
Lock
Magnet
Y32
12
22
10