The RUGGEDCOM RX1501 has passed the following Electromagnetic Compatibility (EMC) and environmental tests.
EMC Type Test for IEC 61850-3
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-29
EMC and Environmental Type Tests
Description
ESD
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Voltage Dips and Interrupts
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC Power Supply
Voltage Dips and Interrupts
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Earth ground ports
Enclosure Ports
AC Power Ports
Signal ports
DC Power Ports
AC Power Ports
Signal ports
DC Power Ports
DC Power Ports
DC Power Ports
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
± 2 kV Line-to-Ground
± 1 kV Line-to-Line
± 4 kV Line-to-Ground
± 2 kV Line-to-Line
10 V
100 A/m, continuous
1000 A/m for 1 s
1000 A/m for 1 s
30% for 1 period
60% for 50 periods
2.5 kV common, 1 kV
differential mode @1 MHz
30 V Continuous
300 V for 1 s
10%
30% for 0.1 s
60% for 0.1 s
Chapter 6
Certification
Severity
Levels
4
a
Note
4
4
3
4
3
a
Note
5
3
4
3
49