RUGGEDCOM RX1501
Installation Guide
Figure 5: Failsafe Alarm Relay Wiring
1. Normally Open    2. Common    3. Normally Closed
Section 2.5

Connecting Power

The RUGGEDCOM RX1501 supports a single high AC, high DC or low DC power module.
Power modules can be equipped with either a screw or European-style (Euroblock) terminal block. The screw
terminal block is installed using Phillips screws and compression plates, allowing either bare wire connections or
crimped terminal lugs. Use #6 size ring lugs for secure, reliable connections under severe shock or vibration.
For information about installing or removing a power module, refer to
Modules".
DANGER!
Electrocution hazard – risk of serious personal injury or death. Make sure the power source is off before
servicing the power module terminal.
IMPORTANT!
• Use minimum #16 gage copper wiring when connecting terminal blocks.
• The maximum wire length between the terminal block and power source must not exceed 6 m (20 ft)
for 24 V power supplies or 18 m (60 ft) for 48 V power supplies.
• For 125/230 VAC rated equipment, an appropriately rated AC circuit breaker must be installed.
• For 125/250 VDC rated equipment, an appropriately rated DC circuit breaker must be installed.
• It is recommended to provide a separate 20 A circuit breaker for each power module module.
• Equipment must be installed according to applicable local wiring codes and standards.