Manual ISOMETER® isoMIL685W–D–P Insulation Monitoring Device with integrated locating current injector for IT AC systems with galvanically connected rectifiers and inverters and for IT DC systems Software version: D440 V 1.28 isoMIL685W-D-P_D00263_04_M_XXEN/03.2021...
Table of contents 1. Important information ................7 5. Mounting ..................... 17 1.1 How to use this manual ..........7 5.1 Common information .
1.2 Technical support 1.2.1 End customer support and advice This manual is intended for qualified personnel working in electrical Technical support by phone or e-mail for all Bender products engineering and electronics! • Questions concerning specific customer applications • Commissioning •...
• Old electrical and electronic equipment from users other than private households Sale and delivery conditions can be obtained from Bender in printed or electronic format. which was introduced to the market after 13 August 2005 must be taken back by the manufacturer and disposed of properly.
Part of the device documentation in addition to this manual is the enclosed "Safety in- Installation inside a control cabinet structions for Bender products". If the ISOMETER® is installed inside a control cabinet, the insulation fault message must be audible and/or visible to attract attention.
DC-supplied loads (such as rectifiers, inverters, variable-speed drives). • Remote diagnosis via the Internet (made available by Bender Service only) • RS-485/BS (Bender sensor bus) for data exchange with other Bender devices via 3.3 Function description Modbus RTU protocol •...
Function Function The insulation monitoring device iso685… is able to measure the insulation resistance 3.4 Insulation fault location reliably and precisely in all common IT systems (unearthed systems). Due to various An additional function of the ISOMETER® in combination with the EDS is the selective in- applications, system types, operating conditions, application of variable-speed drives, sulation fault location.
3.5 Interfaces • Communication protocol Modbus TCP • Communication protocol Modbus RTU • BCOM for communication of Bender devices via Ethernet • BS bus for communication of Bender devices (RS-485) • BB bus (Bender backbone bus) • isoData for recording and managing measured values •...
4. Device overview Device overview 4.1 Dimensions 4.2 Device variants iso685(W)-D… The iso685 variant features a high-resolution graphic LC display and operating controls for direct operation of the device functions. isoxx685(W)-D… It cannot be combined with an FP200. Enclosure iso685…-device familiy – dimensions in mm isoMIL685D-D-P_D00263_04_M_XXEN/03.2021...
Front Rear Connection top Control panel Connction bottom REMOTE interface to connect the FP200(W) * Optional expansion interface for Bender products Bottom Multifunctional I/O interface (see „Connection of the X1 interface“) ETH (X2) Ethernet interface Switchable terminating resistor for termination of the RS-485 interface...
Device overview Device overview 4.4 Display elements and device buttons 4.4.2 device buttons You can adjust the device settings in the respective menu using the menu buttons. De- pending on the menu entry, one of the options displayed below is assigned to the but- tons.
Device overview Device overview 4.5 Operating and navigating 4.5.4 Character input Use the (forward) and (backward) 4.5.1 Menu selection Ethernet x.3.2 buttons to select a character from the dis- Activate the menu by pressing the play. To enter the next character, use the IT system "MENU"...
5. Mounting Mounting 5.1 Common information 5.2 Mounting spaces Only qualified personnel are permitted to carry out the work necessary to install, commission and run a device or system. 20 mm Read the manual before you begin to mount, connect, and commission the unit.
Mounting Mounting 5.3 Screw mounting 5.4 DIN rail mounting 1. Fix the three mounting clips delivered with the device (two of them packed 1. Fix the three mounting clips delivered with the device (two of them packed separately) manually or using a tool, as illustrated below. separately) manually or using a tool, as illustrated below.
6. Connection Connection 6.1 Connection conditions Provide line protection! According to DIN VDE 0100-430, line protection shall be provided for the In accordance with VDE 0100, only qualified personnel are permitted to supply voltage. carry out the work necessary to install, commission and run a device or CAUTION Risk of injury from sharp-edged terminals! system.
Connection Connection 6.2 Connection to a 3(N)AC system 6.3 Connection to an AC system Injury, fire and damage to property due to a short circuit! Injury, fire and damage to property due to a short circuit! According to DIN VDE 0100-430, devices used to protect against short cir- According to DIN VDE 0100-430, devices used to protect against short cir- cuits when terminals "L1/+", "L2"...
Connection Connection 6.4 Connection to a DC system 6.5 Connection to the supply voltage Damage to property due to faulty connection! Injury, fire and damage to property due to a short circuit! The device may be damaged if it is simultaneously connected to the sup- According to DIN VDE 0100-430, devices used to protect against short cir- ply voltage via the "X1"...
Connection Connection 6.6 Connection to the X1 interface 6.7 Connection to the Ethernet interface ETH I1 I2 I3 A B Deactivate RJ45 RS-485 Device I1 I2 high active active Connection with standard patch cable (RJ45/no crossover cable) to other ISOMETER®s or interconnection of several ISOMETER®s in STAR topology via a switch.
6.10 Connection to the BB bus Insert the terminal covers into the recesses provided in the enclosure until they click into The BB bus is an interface that enables Bender devices to communicate with each other. place. The BB bus can be used with an ISOMETER® and one or more EDS44x-S. For this purpose, the BB bus is installed at the rear side of both devices and afterwards, both devices are mounted next to each other on the DIN rail.
Connection Connection 6.11 Connection of EDS44x/IOM441 to the ISOMETER® A maximum of 50 EDS44x devices with one IOM44 each can be connected to an ISOME- TER®. If one EDS and one IOM each are connected via the BB bus, another 49 EDS44x de- vices can be connected to the corresponding IOM441 via the RS-485 interface.
Connection 6.11.5 System structure AC 24 V DC 110 V Input Output A1/+ A2/- L1/+ L3/- KE E EDS441 EDS440 ISOSCAN® ISOSCAN® IT-System PGH ON >20 MΩ >20 MΩ R(an) 40kΩ/10kΩ Application example: monitoring of a control system with the ISOMETER® iso685-D-P and the EDS441-S isoMIL685D-D-P_D00263_04_M_XXEN/03.2021...
7. Commissioning Commissioning 7.1 General initial commissioning process ISOMETER® EDS44x ISOMETER® with EDS44x commissioning commissioning commissioning 1. Check that the ISOMETER® is properly connected to the system to be monitored. Run commissioning wiz- Set BS address on the Set EDS mode in the ISO- 2.
Commissioning Commissioning 7.2 Initial commissioning 7.2.3 Setting system type By setting the system type, the insulation monitoring device can be optimally adapted to Check network function! the system to be monitored. The system type is essential information for the insulation When the device has been integrated into a network, the influence on the monitoring device in order to determine the insulation resistance correctly.
Commissioning Commissioning 7.2.6 Setting EDS current 7.3 Commissioning of EDS Set the maximum locating current. Proceed as follows to put into operation an EDS after commissioning the ISOMETER®: EDS441: 1-5 mA 1. First, search for all available measuring channels. EDS440: 10-50 mA Menu path: Menu ->...
Commissioning Commissioning 7.4 Recommissioning If the device has already been put into operation once, the self test will be carried out shortly after connecting the supply voltage. The commissioning wizard will not restart. You can restart the commissioning wizard using the following menu path: Menu ->...
8. Display Display 8.1 Standard display 8.2 Fault display (active) During normal operation, the ISOMETER® displays the message "OK" and below, the cur- An active fault is displayed by rently measured insulation resistance. The upper part of the display turns orange and displays the fault message. Depending on the type of fault, the LEDs "ALARM 1", "ALARM 2"...
Display Display 8.3 Fault display (inactive) 8.4 Acknowledging a fault message An inactive fault is indicated by . If several faults have occurred, the number of faults In order to acknowledge the fault message and return to the ISOMETER®'s standard dis- will also be indicated.
Display Display 8.5 Data-isoGraph 8.7 ISOnet operation The isoGraph represents the chronological sequence of the insulation resistance over The ISOMETER® displays the message „ISOnet active“ when the ISOMETER® is in ISOnet time. This graphical representation can be displayed over the following time periods: mode but is not currently measuring.
Display Display 8.9 Automatic test * Display for low-frequency measurements In the LAB procedure, the pulse can last up to one minute. Therefore, there If the ISOMETER® measures in ISOnet mode, the "ON" LED flashes and the measurement is no constant "changing" of the display symbols. The respective symbols progress bar in the lower right corner pulses.
Settings Settings 9.2 Settings in the device menu 3. Data meas. values 4. Control 1. TEST Representation of the menu items in the headings 2. Reset 3. Initial Measure The settings of the ISOMETER® are explained in the order of the device 4.
Suitable for systems with extremely low frequency controls in the •Inverter < 10 Hz (1.2) DC alarm range 0.1…460 Hz. Enables the Bender service to make customer-specific settings. •Customer-specific The DC alarm is triggered in the event of a DC offset voltage (U ) in the system.
Settings Settings (1.6.1) ISOloop The exemplary wiring diagram shows how the digital inputs can be wired. Turns the function on or off. (1.6.2) Measured value subscription Deactivate RS-485 Device I1 I2 When the measured value subscription and the ISOloop function are activated, the mea- high sured values of the active measuring device are distributed within the team and shown active...
Settings Settings (1.10.1.3) t(off) (1.11.1.2) Relay mode The response time t(off) after a switch-off signal can be set between 100 ms and 300 s. The relay mode can be adapted to the application: (1.10.1.4) Function Normally closed - N/C operation contacts 11-12-14 / 21-22-24 (in •N/C fault-free condition, the alarm relay is energised).
Settings Settings (1.11.3) Digital 1 Function Description The following parameters can be set for each of the digital outputs: The status of the output changes in case of an earth fault in the direction •DC+ alarm of DC+ when 25 % of the value are exceeded. This does not concern sym- (1.11.3.1) TEST metrical faults.
Settings Settings (1.11.3.3) Function 1 (1.11.6.1) Mode Refer to chapter 9.2 (1.11.1.3) “Function 1”, page 42f. The following values can be set for the operating mode of the analogue output (1.11.3.4) Function 2 Refer to chapter 9.2 (1.11.1.3) “Function 1”, page 42f.
Settings Settings Calculation of the insulation resistance using the analogue output: (2.0) EDS (insulation fault location) (2.1) General Lower value Upper value ) * R Analogue Output A Analogue Output A (2.1.1) Current 0 mA 20 mA 4 mA 20 mA Risk of malfunctions due to excessive locating current on sensitive 0 μA 400 μA...
Settings Settings (2.1.5) Scan for channels: Inactive insulation fault location The function determines how the "Scan Channels" process is triggered. (insulation measurement) New insulation fault A channel scan searches the BS and BB bus for existing (detected) EDS devices. These are No insulation fault Mode: auto/1 cycle continuously assigned to the Modbus registers internally.
Settings Settings Multiple selection is possible. (2.4.1.1) Current transformer (CT) Set the used current transformer. All measuring channels are selected. •Select all No channel is selected. •No selection W…/WR…/WS…/ •Type A The current selection is inverted. •Invert selection W/WS8000 •Channel 1 (BS 2/1) A single channel is selected.
Settings Settings (2.4.2) Outputs (2.4.2.1.3) Function 1 Make settings for the outputs of the EDS and the IOM441-S. Up to three functions can be assigned to one output. The functions are linked to an OR operator: •Common relays •Channel relays Funktion 1 •Buzzers Funktion 2...
Settings Settings (2.4.2.3) Buzzers (2.4.2.7) Function 3 Select the buzzers that you would like to configure. Refer to “9.2 (2.4.2.1.3) Function 1”. (2.4.3) Dig. input All buzzers are selected. •Select all No buzzer is selected. •No selection Select the digital inputs of the EDS that you would like to configure: The current selection is inverted.
Settings Settings (2.4.4.1) System type (2.4.4.4) Fault memory Faults that only occur temporarily can be saved. Settings made to this menu item will only have an effect on connected After eliminating the cause of fault, alarm messages remain stored until a •on EDS460 and NOT on EDS44x devices.
“9.2 (2.4.4.4) Fault memory”. (2.6.4.1) TEST (2.9) Service Refer to “9.2 (2.4.2.1.1) TEST”. The service menu can only be accessed by Bender service staff. (2.6.4.2) Function 1 Refer to “9.2 (2.4.2.1.3) Function 1”. (2.6.4.3) Function 2 Refer to “9.2 (2.4.2.1.3) Function 1”.
Settings Settings (3.0) Data measured values (4.4) EDS The ISOMETER® stores certain measured values for a specific period of time. You can view Starts an insulation fault location process on the connected EDS device thes data at the "Data meas. values" menu item. Navigate through the different views (4.5) Device: using the buttons:...
Page 53
Settings Settings (6.2.3) Summer time (6.3.1) Write access Summer time can be considered in the following settings: Set whether the device can be parameterised externally via Modbus or web server. Dis- playing and reading out data via Modbus and web server is always possible, regardless of No automatic change between summer time and standard time.
Page 54
If a DNS server is used, enter the server's IP address. For questions regarding the configu- (6.3.5) RS-485 ration of a DNS server, contact your network administrator. Set the parameters for communication with other devices via the Bender sensor bus. (6.3.2.6) Domain Selecting an RS-485 protocol 1.
Page 55
Enter a 4-digit Service Profile PIN 1. Profile: Activation of special customer profiles by Bender. The device is first configured by the Bender service and the configuration is saved in a service profile. Activating this profile causes a warning message. The customer can activate it as a customer-specific profile by entering a Service Profile PIN.
Page 56
– Easy and fast parameterisation of the device menu item "Allow" must have been set in the "Write access" menu. – Easy assignment and editing options of device texts • Maintenance – Data storage of specific events for fast support by the Bender service isoMIL685D-D-P_D00263_04_M_XXEN/03.2021...
Page 57
Device communication Device communication 10.4.3 User interface 10.4.4 Menu structure The web menu is located on the left side of the browser window. Activated menu items are either highlighted in YELLOW or written in YELLOW. Use the scroll bar on the right side to display further menu items.
Page 58
Device communication Device communication 10.4.5 Parameter changes 10.4.5.3 Error detection in case of incorrect entry In some cases, the system expects certain characters to be entered, for example, CAPITAL 10.4.5.1 Display of parameters in standard versions LETTERS. In case of an incorrect entry, the corresponding field is coloured in RED. Inputs are located horizontally (orange frame) and the corresponding parameters ver- tically (blue frame).
Page 59
Device communication Device communication 10.4.6 Changing parameters in the web browser 10.4.7 Changing parameters in the device menu when the web browser is open Changed values are highlighted in YELLOW in the input field (see fig. 2.1). Changes can If values are changed in the iso685 device menu, the changed values are not au- be made via drop-down menu, value input or text input.
Page 60
The optimum cable routing for the BS bus is a double-terminated bus topology. The The BS bus is used to extend Bender measuring devices (e.g. ISOMETER®) It is an RS-485 in- length of the branch line is limited to 1 m. These branch lines do not have to be terface with a specially developed protocol for Bender devices.
Page 61
BMS protocol. To evaluate the data by means of a PC or laptop, an USB/RS232-RS485 interface converter are required. Contact Bender Service to receive this device. Interface data: • The RS-485 interface, galvanically isolated from the device electronics •...
Page 62
Device communication 10.7.1 isoData-protocol table Description Length [Bytes] Value Unit Example string Mode Data packet start character for modes 2 and 3 Data packet start character 0x02 0x02 for mode 1 Available Bitmask Dependent on the fields included. (Bitmask) FFFFFFFF Date Current date dd.mm.yy...
Page 63
Device communication Description Length [Bytes] Value Unit Example string Mode Voltage between phase L2 and PE. Voltage U (VRMS) L2-PE 1234 RMS value, Note: always signed with '+' Voltage between phase L3 and PE. Voltage U (VRMS) L3-PE 1234 RMS value, Note: always signed with '+' Quality of measured value 0 % = Poor quality Measurement quality...
Page 64
Device communication Description Length [Bytes] Value Unit Example string Mode 0 == No alarm Alarm message Insualtion fault 1 == Alarm 1 Number Brief overview 2 == Alarm 2 3 == Alarm 1 + Alarm 2 Temperature in device Temperature value preceeded by '+' or '-' sign °C +100 System frequency...
Page 65
11. Insulation fault location Insulation fault location 11.1 General description An additional function of the ISOMETER® in combination with the EDS is the selective in- sulation fault location. The insulation faults detected in the IT system by the ISOMETER® can be located by means of an EDS and a measuring current transformer. For further information regarding the function principle of the insulation fault location, refer to chapter 3.4 „Insulation fault location“.
Page 66
12. Special functions for coupled IT systems Special functions for coupled IT systems 12.1 Particularities when monitoring coupled IT systems 12.2 System isolation via digital input with two coupled systems When using ISOMETER®s in IT systems, make sure that only one active ISOMETER® is con- nected in each interconnected system.
Page 67
Special functions for coupled IT systems Special functions for coupled IT systems 12.3 System isolation via ISOnet 12.3.1 Systempictures The ISOnet function ensures via an Ethernet connection that only one ISOMETER® of the interconnection is active when several ISOMETER®s are connected to an IT system. For several ISOMETER®s to be able to measure in the same ISOnet interconnection, the settings for the BCOM system name and the BCOM subsystem have to be the same.
Page 68
Special functions for coupled IT systems Special functions for coupled IT systems 12.3.2 Configuration and function 12.4 ISOloop For the ISOnet function, the following settings are made in the menu: Alarm settings Ring systems are a special type of coupled systems in which all systems can be coupled ->...
Page 69
The basis of the ISOloop function is the combination of several ISOMETER®s to form an in- terconnection. The grouping of up to 10 ISOMETER®s is carried out with a separate soft- ware, the BCOM Group Manager. The program can be downloaded from the Bender website at www.bender.de/service-support/downloads or via the web server ("Menu" >...
Page 70
Special functions for coupled IT systems Special functions for coupled IT systems The "Connection List" must contain all connections that exist in the installation. The follo- 12.4.2.3 Transferring the configuration file to an ISOMETER® wing figure shows the connections for the above example. The configuration file is installed via the web user interface of the iso685-x-P device in the browser of a computer in the network.
Special functions for coupled IT systems Special functions for coupled IT systems After completion, the file is available for download in the download area of each 12.5 EDSsync device: In combination with the EDS, the ISOMETER® iso685-x-P offers the function of selective in- sulation fault location.
BCOM manual (D00256) at vices from different subnets can also be combined into a group. Each combination of www.bender.de/service-support/downloads. subnet and device address may only exist once in an interconnection. 12.5.2 Creating groups with the BCOM Group Manager The BCOM Group Manager provides help for creating ISOMETER®...
Special functions for coupled IT systems Special functions for coupled IT systems After all settings of the group have been made, the configuration file must be saved. 7. Select target folder "group" (1.) 8. Select file "grp_0101.cfg" in the respective folder of your source PC (2.) 9.
13. Alarm messages 13.1 Measured value alarms Alarm messages are activated directly after switching on and can occur immediately. Alarm message Description Measures LED indicators An insulation fault exists. The insulation resistance falls • Observe insulation resistance in the monitored system Insulation fault "ALARM 1"...
Internal device error • Switch the supply voltage off and on "SERVICE" is lit • Contact Bender service • Check insulation fault and eliminate fault of DC compo- DC offset voltage There is a DC offset voltage in the system.
Alarm messages 13.4 ISOloop These messages only become active after activating the ISOloop function. Alarm message Description Measures LED indicators • Make sure that all devices in the group to be configured The ISOloop group configuration is not uniform for all are able to communicate (correctly set and BCOM and ISOloop configuration is not devices in the group or one of the devices has no configura-...
Alarm messages Alarm message Description Measures LED indicators • Check wiring of the measuring current transformers One measuring current transformer has not been con- • Check device function Interference CT connection nected correctly or does not work. • Start new search for EDS channels •...
– – – – tings. If no settings have been made by the Bender service, the profile has the same parameters as the "Power circuits" profile. For response times, refer „Device profiles“ at the follwing sections. Switching between profiles * Low-frequency system voltages When switching a profile, the value of R is reset.
Technical data Technical data 14.2 Diagrams 14.2.1 Response time profile power circuits 14.2.3 Response time generator profile Response time depending on response value and system leakage capacitance Response time depending on response value and system leakage capacitance acc. to IEC 61557-8 (U = 690 V, f = 50 Hz) measuring range <...
Technical data Technical data 14.2.5 Response time inverter > 10 Hz profile 14.2.7 Response time DC alarm Response time depending on response value and system leakage capacitance Typical response times DC alarm at R depending on the measurement profile acc. to IEC 61557-8 (U = 690 V, f = 50 Hz) measuring range <...
Technical data Technical data 14.3 Factory settings isoMIL685W-D-P Parameter Value Switching elements Parameter Value Relay 1 Response values/alarms Test Response value R (ALARM 1) 40 kΩ Relay mode N/C operation Response value R (ALARM 2) 10 kΩ Function 1 Ins. alarm 1 DC alarm Function 2 Connection fault...
Technical data Technical data 14.4 Tabular data isoMIL685W-D-P Supply via X1: Supply voltage U ....................................DC 24 V Insulation coordination acc. to IEC 60664-1/IEC 60664-3 Tolerance of U ................................DC -20…+25 % Definitions: IT system being monitored Measuring circuit (IC1)..............................(L1/+, L2, L3/-) Nominal system voltage range U ......................
Page 83
Technical data Technical data Display Interfaces Indication........................graphic display 127 x 127 pixels, 40 x 40 mm Field bus: Interface/protocol............................web server/Modbus TCP/BCOM Display range measured value............................0.1 kΩ…20 MΩ Operating uncertainty (acc. to IEC 61557-8)........................±15 %, min. 1 kΩ Data rate................................10/100 Mbit/s, autodetect Max.
Technical data Technical data Environment/EMC and temperature ranges Other EMC....................................IEC 61326-2-4 Operating mode................................continuous operation Operating temperature.................................-25…+70°C Mounting position (0°)................display-oriented, cooling slots must be ventilated vertically ................................-40…+85°C (for UL applications) Degree of protection internal components ............................IP40 Transport....................................-40…+85 °C Degree of protection terminals ................................IP20 Long-term storage ................................
15. Glossary Glossary BB bus The BB bus is an interface which enables Bender devices to communicate Subsystem (BCOM) The subsystem structures parts of the system as units defined by the cus- with each other (Bender-internal device bus). tomer, e.g. all PQ devices. A typical subsystem are also "non BCOM-capa- The BB bus can be used with an ISOMETER®...