External Checks:
Check for leaks with the following recommended checks. Re-pressurize the container to 2 inches water gauge and
look for leaks at the following areas using soapy water (mixture of dish detergent and water) looking for bubbles.
Inspect the evaporator unit access panels. Check that gasket is properly in place. Tighten the access panel
bolts to 60 inch-lbs. and caulk if necessary.
Inspect the defrost drain outlet line. If it is leaking, complete other checks and re-inspect internally.
Inspect the unit / container box joints. Caulk if necessary.
Inspect the through-wire bulkhead connections. Secure and caulk if required.
Inspect the container floor drains under the container (if accessible). If leaking is observed, complete exter-
nal checks and reinspect internally.
Inspect the rear door seals. Ensure the curtain is properly installed (curtain should be visible throughout the
perimeter of the doors if installed without a curtain track). Remove and install a new curtain. De-pressurize
the container prior to opening the container.
Ensure Manual Fresh Air Panel is equipped with collars
Internal Checks:
Remove pressure within the container and perform the inspections listed below. On completion of the checks and
any associated repairs, it is recommended to test the unit again to verify it now meets the required level.
Inspect the curtain for any rips. Replace the curtain.
Inspect the container floor drains. Ensure they are properly sealed. Standard drains can not be used.
Inspect the defrost drain outlet line. Confirm the drain line is filled with water.
Inspect for any internal wall damage. Repair and caulk as required
Inspect floor to side wall joint, floor to front bulkhead joint for any damage. Repair and caulk as required

Figure 6.3 Magnehelic Gauge (Kit # 07-00177-20)

Figure 6.4 Fresh Air Panel Collars

Fresh Air Panel
6–3
Start Timer*
Shut Off Air Supply
Check Container for
Leaks
* 40' Container - at least 4 minutes
(Figure
6.4), part number 79-04064-00.