10. Disconnect the WDV by turning the WDV with a 3/4" wrench and using a 9/16" wrench to hold the mating
connector.
11. To install, follow removal steps in reverse. Make sure to apply a Teflon paste to the brass fitting when re-fit-
ting the WDV to the manifold. Ensure that no Teflon gets into the fitting.
12. Reconnect the VPS apply cable tie and refit the access panel.
5.3.2

Replacing the Particulate Air Filters

1. Open the panel needed to gain access to the particulate air filters
accessed from the front of the unit through the upper left access panel, or from inside the container through
the EverFRESH access panel door.
2. Remove both filter housings by turning counterclockwise until free. Carefully lay down each housing to pre-
vent damage to evaporator fins. When removing the second filter housing, the filter will come off with the
housing.
T-374
(Figure
5–18
5.1). This component can be