Electronic Modules
3.2 Input and Output Modules of the Modular Devices

Input and Output Module IO240

3.2.20
3.2.20.1

Description

The following terminals are on the input module IO240 for the low-power instrument transformer (LPIT):
4 current inputs for the low-power current transformers in the gas insulated switchgears (GIS LPCT), for
example, rogowski coils
4 voltage inputs for the low-power voltage transformers in the gas insulated switchgear (GIS LPVT), for
example, capacitive voltage sensors
4 temperature measuring channels (4-wire PT100 thermistor)
The connections are distributed over four 14-pole terminal blocks.
3.2.20.2

Terminals

Overview of Terminals
[le_IO240_overview, 1, --_--]
(1)
Current/Voltage/Temperature terminal xA
(2)
Current/Voltage/Temperature terminal xB
(3)
Current/Voltage/Temperature terminal xC
(4)
Current/Voltage/Temperature terminal xD
(5)
Protective grounding terminal
(6)
LPIT cable shield
NOTE
i
i
x corresponds to the slot in the 19-inch rack.