Technical Data

6.1 Analog Inputs

6.1
Analog Inputs
Current Inputs
All current, voltage, and power data are specified as RMS values.
Rated frequency f
Protection-class current trans-
formers
Instrument transformers
Burden for rated current
Thermal rating
(protection and instrument trans-
formers)
Dynamic load-carrying capacity
GIS Low-Power Current Input (via Module IO240)
All current, voltage, and power data are specified as RMS values.
Rated frequency f
Rated current I
rated
Rated current I
rated
Measuring range
Power consumption per current
circuit at rated current
Thermal rating
Accuracy
Voltage Input
All current, voltage, and power data are specified as RMS values.
Rated frequency f
Input and output modules
Measuring range
Burden
Thermal rating
220
50 Hz, 60 Hz
rated
16.7 Hz (for rail protection devices only)
Rated current I
5 A
1 A
5 A
1 A
Approx. 0.1 VA
20 A continuously
25 A for 3 min
30 A for 2 min
150 A for 10 s
500 A for 1 s
1250 A one half wave
50 Hz
rated
60 Hz
- 50 Hz
Min. 13 mV
Max. 332 mV
- 60 Hz
Min. 15.4 mV
Max. 386 mV
50 ⋅ I
rated
1.6 ⋅ I
rated
Max. 40 mVA
Burden = 9.5 kΩ
Max. input voltage = 20 V
Class 5TPE (Protection channel)
Class 0.2S (Metering channel)
50 Hz, 60 Hz
rated
16.7 Hz (for rail devices only)
IO102, IO202, IO208, IO211,
IO214
0 V to 200 V
< 0.1 VA
230 V continuously
Measuring range of
rated
the modular devices
0 A to 500 A
0 A to 100 A
0 A to 8 A
0 A to 1.6 A
(Protection channel)
(Metering channel)

SIPROTEC 5, Hardware Description, Manual

Measuring range of the
non-modular devices
0 A to 250 A
0 A to 50 A
0 A to 8 A
0 A to 1.6 A
IO215
0 V to 7.07 V
< 0.01 VA
20 V continuously