GIS Low-Power Voltage Input (via Module IO240)
All current, voltage, and power data are specified as RMS values.
Rated frequency f
Rated voltage V
Rated voltage V
Measuring range
Power consumption per current
circuit at rated current
Thermal rating
Accuracy
NOTE
i
i
For more information on the technical data of the current and voltage transformers, refer to the Technical
Data chapter in the SIPROTEC 5 Device manuals.
Measuring-Transducer Inputs (via Module ANAI-CA-4EL)
Insulation class
Connector type
Differential current input channels
Measuring range
Fault
Input impedance
Conversion principle
Permissible potential difference
between channels
Galvanic separation from ground/
housing
Permissible overload
Measured-value repetition
Inputs for Optical Sensors for Arc Protection (via Module ARC-CD-3FO)
Connector type
Number of transceivers
Fiber type
Receiver
Maximum
Minimum
Spectrum
Attenuation
Optical budget
Analog sampling rate
ADC type
18
All values in combination with sensors approved by Siemens.
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-J, Edition 08.2020
50 Hz
rated
60 Hz
- 50 Hz
Min. 0.25 mA
rated
Max. 2.00 mA
- 60 Hz
Min. 0.30 mA
rated
Max. 2.20 mA
2 ⋅ V
rated
Max. 1 mVA
Burden = 50 Ω
Max. input current = 4.4 mA
Class 0.1
SELV (Safety Extra Low Voltage) (according to IEC 60255-27)
8-pin terminal spring
4
DC -25.6 mA to +25.6 mA
< 0.5 % of the measuring range
140 Ω
Delta-sigma (16 bit)
DC 20 V
DC 700 V
DC 100 mA continuously
200 ms
AVAGO AFBR-4526Z
3
Plastic Optical Fiber (POF) 1 mm
-10 dBm ± 2 dBm
-40 dBm ± 2 dBm
400 nm to 1100 nm
In the case of plastic optical fibers, you can expect a path attenuation of
0.2 dB/m. Additional attenuation comes from the plug and sensor head.
Minimal 25 dB
18
16 kHz
10-bit successive approximation
Technical Data
6.1 Analog Inputs
221