Siemens SIPROTEC 5 V8.30 Manual page 53

Table of Contents

Advertisement

[tdps201x-270812-01.tif, 1, en_US]
Figure 3-3
Time-Synchronization Terminal
The terminal for time synchronization is located on the D-sub 9 interface (position G). Time synchronization
signals for DC 5 V, DC 12 V, and DC 24 V can be processed as an option.
For further information on connecting to the time synchronization, see chapter
in the Technical Data.
On-Site Operation Panel Terminal
The terminal for the on-site operation panel of surface-mounted devices is located on the D-sub 15 interface
(position H). The on-site operation panel of surface-mounted devices with the on-site operation panel inte-
grated or detached is connected to this interface.
For further information on connecting to the on-site operation panel, see chapter
faces
in the Technical Data.
Integrated Ethernet Interface J(RJ45)
This terminal is used to load the device with DIGSI 5 using Ethernet. This terminal also enables straightforward
IEC 61850 Ethernet communication or communication with another protocol via Ethernet, for example, for
connecting an external RTD unit.
For further information on the integrated Ethernet interface, see chapter
Technical Data.
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-J, Edition 08.2020
PS201 – Connection Diagram
3.1 Power-Supply Modules of the Modular Devices
6.6 Communication Interfaces
6.6 Communication Inter-
6.6 Communication Interfaces
Electronic Modules
in the
53