Siemens SIPROTEC 5 V8.30 Manual page 187

Table of Contents

Advertisement

Always fit the on-site operation panels of the expansion modules from left to right.
Always fit the on-site operation panel of the expansion module with the key switches in the 1st place
next to the on-site operation panel of the base module.
Always fit the on-site operation panels without LEDs last.
Join the on-site operation panels to one another with 2 mounting brackets.
Always install a power-supply module PS203 on the right as the first unit in the 2nd device row.
Note that the PS203 must always have the same rated voltage as the base module.
Always mount the redundant power-supply module PS204 at the very right in the corresponding row
(seen from the front). If a CB202 PCB assembly is used in the row, this CB202 PCB assembly must always
be plugged on the right of the power-supply module PS204 (at the very right). You can find an example
for this in chapter
Note that the power-supply module PS204 must always have the same rated voltage as the base module.
In the 2nd device row, you do not need any on-site operation panels, mounting brackets, or distance
frames.
NOTE
i
i
When expanding a device in the 1st device row, order 2 mounting brackets that match the width of the
expanded device.
[dwauize1-040211-01.tif, 2, --_--]
Figure 5-5
(1)
Distance frame
(2)
Mounting bracket
(3)
Distance frame on base module rotated by 180
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-J, Edition 08.2020
3.1.4.2 Positioning
Device Row
Specifications.
o
Working on the Device
5.2 Expanding Modular Devices
187

Advertisement

Table of Contents
loading

Table of Contents