Siemens SIPROTEC 5 V8.30 Manual page 225

Table of Contents

Advertisement

Integrated Power Supply
Power consumption (life relay active)
1/3 module, non-modular
Without plug-in modules
1/3 base module, modular
Without plug-in modules
1/6 expansion module
1/6 plug-in module
assembly without plug-in
modules (modules CB202)
Plug-in module for base
module or plug-in module
assembly (for example,
communication module)
Stored-energy time for auxiliary voltage outage or
short circuit, modular devices
IEC 61000-4-11
IEC 61000-4-29
Stored-energy time for auxiliary voltage outage or
short circuit, non-modular devices
IEC 61000-4-11
IEC 61000-4-29
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-J, Edition 08.2020
DC
7 W
13 W
3 W
3.5 W
< 5 W
AC 230 V/50 Hz
16 VA
55 VA
6 VA
14 VA
< 6 VA
For V ≥ DC 24 V ≥ 50 ms
For V ≥ DC 110 V ≥ 50 ms
For V ≥ AC 115 V ≥ 50 ms
For V ≥ DC 24 V ≥ 20 ms
For V ≥ DC 60 V ≥ 50 ms
For V ≥ AC 115 V ≥ 200 ms
Technical Data
6.2 Supply Voltage
AC 115 V/50 Hz
12.5 VA
40 VA
6 VA
7 VA
< 6 VA
225