Plug-In Module
1 x optical serial, 820 nm, ST connector,
2 km via 62.5/125 μm multimode optical
fiber
2 x optical serial, 820 nm, ST connector,
2 km via 62.5/125 μm multimode optical
fiber
2 x electrical Ethernet 100 Mbit/s, RJ45,
20 m
2 x optical Ethernet 100 Mbit/s,
1300 nm, LC connector, 24 km via
9/125 μm singlemode optical fiber
2 x optical Ethernet 100 Mbit/s,
1300 nm, LC connector, 2 km via
50/125 μm or 62.5/125 μm multimode
optical fiber
1 x optical serial, 1300 nm, LC
connector, 24 km via 9/125 μm single-
mode optical fiber or 4 km via 62.5/125
μm multimode optical fiber
2 x optical serial, 1300 nm, LC
connector, 24 km via 9/125 μm single-
mode optical fiber or 4 km via 62.5/125
μm multimode optical fiber
1 x optical serial, 1300 nm, LC
connector, 60 km via 9/125 μm single-
mode optical fiber
2 x optical serial, 1300 nm, LC
connector, 60 km via 9/125 μm single-
mode optical fiber
1 x optical serial, 1550 nm, LC
connector, 100 km via 9/125 μm single-
mode optical fiber
2 x optical serial, 1550 nm, LC
connector, 100 km via 9/125 μm single-
mode optical fiber
1 x optical serial, bidirectional via
1 common optical fiber, 1300 nm/
1550 nm (Tx/Rx), 2 x LC simplex plug,
40 km via 9/125 μm singlemode optical
fiber
2
For modular devices only (not for 7ST85 and 6MD89)
1
USART-AH-1LDFO only in connection with USART-AJ-1LDFO or USART-AY-2LDFO
2
3
USART-AJ-1LDFO only in connection with USART-AH-1LDFO or USART-AX-2LDFO
USART-AX-2LDFO only in connection with USART-AJ-1LDFO or USART-AY-2LDFO
4
USART-AY-2LDFO only in connection with USART-AH-1LDFO or USART-AX-2LDFO
5
6
For the 2 x electrical Ethernet and 2 x optical Ethernet over 24 km function, separate SFPs are necessary. These can be ordered as
accessories.
SIPROTEC 5, Hardware Description, Manual
C53000-G5040-C002-J, Edition 08.2020
6
6
■ ■
Plug-In Modules
4.2 Communication Modules