Page 1
NE or F&G/ND Load, with Diagnostic & Universal Fault Mirroring DIN-Rail and Termination Board, Model D5096S-100 D5096-100 - 5 A SIL 3/SIL 2 SC3 - Relay Module for NE or F&G/ND Load with Diagn. & Univ. Fault Mirroring G.M. International ISM0439-6...
General Description: The D5096S-100 is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed. 2 for high risk industries. It provides isolation between input and output contacts. A wide compatibility towards different DCS/PLC is guaranteed: driving line pulse testing, executed by DCS/PLC, is permitted by a dedicated internal circuit, to prevent relay and LED flickering.
Ordering information Power Bus and DIN-Rail accessories: Model: D5096S-100 Bus Connector JDFT049 Bus Mounting Kit OPT5096 Front Panel and Features SIL 3 (low demand mode of operation) for NE Load according to IEC 61508:2010 Ed.2 with Tproof = 14 / 20 yrs (≤ 10 / >10 % of total SIF) and PFDavg (1 year) = 7.02 E-06, SFF = 99.61 %.
Function Diagram SAFE AREA, ZONE 2 GROUP IIC T4, NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, GROUPS A, B, C, D T-Code T4 MODEL D5096S-100 Load and Supply 24 Vdc Line Diagnostic NC Service Load Not SIL Fault Out (35 V, 100 mA)
Operation The single channel 5 A Relay Output D5096S-100 is a relay module suitable for the switching of safety related circuits, up to SIL 3 level according to IEC 61508:2010 Ed.2 for high risk industries. It provides isolation between input and output contacts. D5096S-100 has 2+2 SPST relay contacts connected in parallel and then in series to avoid spurious trip and to Increase availability (see function diagram).