GMI D5095S Safety Manual

GMI D5095S Safety Manual

5 a sil 3 nc contact relay output module for ne or f&g/nd load, din-rail and termination board

Advertisement

D5095S
SAFETY MANUAL
5 A SIL 3 NC contact Relay Output Module
for NE or F&G/ND Load,
DIN-Rail and Termination Board, Model D5095S
Reference must be made to the relevant sections within the instruction manual ISM0300,
which contain basic guides for the installation of the equipment.
D5095S - 5 A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load
G.M. International ISM0307-1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the D5095S and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for GMI D5095S

  • Page 1 Reference must be made to the relevant sections within the instruction manual ISM0300, which contain basic guides for the installation of the equipment. D5095S - 5 A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load G.M. International ISM0307-1...
  • Page 2 When D5095S drives NE Load and operates in High Demand mode: PFH = λ = 3.10 E-09 h - Valid for SIL 3. SC 3: Systematic capability SIL 3. D5095S - 5 A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load G.M. International ISM0307-1...
  • Page 3 When D5095S drives F&G/ND Load and operates in High Demand mode: PFH = λ = 1.96 E-09 h - Valid for SIL 3. SC 3: Systematic capability SIL 3. G.M. International ISM0307-1 D5095S - 5 A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load...
  • Page 4 When D5095S drives NE Load and operates in High Demand mode: PFH = λ = 3.10 E-09 h - Valid for SIL 3. SC 3: Systematic capability SIL 3. D5095S - 5 A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load G.M. International ISM0307-1...
  • Page 5 When D5095S drives F&G/ND Load and operates in High Demand mode: PFH = λ = 1.96 E-09 h - Valid for SIL 3. SC 3: Systematic capability SIL 3. G.M. International ISM0307-1 D5095S - 5 A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load...
  • Page 6 = relay2; dip3 = relay3; dip4 = relay4) WARNING: after T-proof test, dip-switch 1-2-3-4 must be set to “OFF” position for normal operation. D5095S - 5 A SIL 3 NC contact Relay Out Module for NE or F&G/ND Load G.M. International ISM0307-1...