8 OUTER CASE FITTING

 Place the case over the engine.
Make sure that the channel near the top
of the rear of the outer case locates fully
into the wings of the engine back panel.
See figure 11.
 Fit the control knob firmly on to
the control spindle.
 Refit the two case retaining screws
at the front of the case near the bottom
corners.
Figure 11. Case top location

9 SPILLAGE CHECK

A spillage test must be made before the installed appliance is left with the
customer.
1. Close all doors and windows in the room containing the fire.
2. Light the appliance and set the control knob to the maximum position (Position 5).
3. Leave the appliance on for five minutes.
4. Place a smoke match tube (with lighted
match) horizontally underneath the radiant box
but touching the top lip of the box. The tube
should be between the two vertical inner ribs of
the centre radiant. The tip of the match should
project between 2mm and 5mm beyond the
lowest edge of the radiant box lip. See figure
12.
5. The installation is satisfactory if the smoke is
drawn into the appliance. If the smoke is not
drawn into the appliance, leave the appliance
alight at the maximum setting for a further ten
minutes and then repeat the test. If the smoke is
still not drawn into the appliance, inspect the
sealing of the closure plate. If the sealing is
Figure 12. Spillage check
satisfactory but the appliance is installed with
Page 18