Tecnoware EVO DSP PLUS TT 10.0 User Manual page 34

Table of Contents

Advertisement

Available languages

Available languages

ENGLISH
ECO Mode
Voltage Range
Frequency Range (50 Hz)
Frequency Range (60 Hz)
BATTERIES
Battery Type
Number of batteries
Nominal Battery Voltage
Battery Charge Time (typical)
Expandable Autonomy
ENVIRONMENTAL CONDITIONS
Storage Temperature Range
Operating Temperature Range
Relative Humidity Range
Max. Altitude
Protection level
Cooling
Audible Noise (at 1 meter)
STANDARDS
Safety
Performance
EMC
Product certification
COMMUNICATIONS
Computer Interface
Software
SNMP Interface
OTHERS
EPO (Emergency Power OFF)
Dry Contact Interface
Manual Bypass for Maintenance
Parallel Operating Mode
ECO Mode
Frequency Converter Mode
User's manual
Lower Limit: 5÷10 % (selectable); upper Limit: 5÷10 % (selectable)
Lower Limit: 46÷48 Hz (selectable); upper Limit: 52÷54 Hz (selectable
Lower Limit: 56÷58 Hz (selectable); upper Limit: 62÷64 Hz (selectable
Lead acid, sealed, free maintenance
20/40
Available, through external Battery Box (optional)
-25°C to +55°C (-15°C to 40°C recommended for longer Battery life)
0°C to +40°C (20°C to 25°C recommended for longer Battery life)
< 58 dBA
Low Voltage (Safety) Directive 2014/35/EU
EMC (Electro-Magnetic Compatibility) Directive 2014/30/EU - category C3
Included UPS Management Software,
compatible with: Windows, Mac OS X, Linux, Unix, etc.
Technical data may change without prior notice
30
40
240 Vdc
6-8 hours
0% - 95% (non condensing)
3000 m
IP 20
Fan cooling
< 60 dBA
IEC 62040-3
CE
1 RS232 port and 1 USB port
Optional
Included
Optional
Included
Optional (up to 3 UPS)
Selectable
Selectable
UPS EVO DSP PLUS TT 10.0-15.0-20.0-30.0 pf. 0,9
60