10 Technical Characteristics

UPS EVO DSP PLUS TT Model
Power
Nominal Active Power
Power Factor
Technology
Dimension (W x H x D) mm
INPUT
Number of phases
Nominal Voltage (Phase-Phase)
Nominal Voltage (Phase-Neutral)
Lower Limit
Voltage Range for
Normal mode
Upper Limit
Nominal Frequency
Frequency Range (Normal mode)
Total Harmonic Distortion Input (THDi)
Input Power Factor
OUTPUT
Number of phases
Nominal Voltage (Phase-Phase)
Nominal Voltage (Phase-Neutral)
Voltage Regulation
Inverter Waveform
Nominal Frequency
Free Running Frequency (Battery mode)
Total Harmonic Distortion (THD)
Crest Factor
Overload (Normal mode)
Overload (Battery mode)
(Normal <--> Battery)
Transfer Time
(Battery <--> Bypass)
(Normal <--> Eco)
BYPASS Mode
Number of phases
Nominal Voltage (Phase-Phase)
Nominal Voltage (Phase-Neutral)
Voltage Range (Phase-Neutral)
Frequency Range (50 Hz)
Frequency Range (60 Hz)
UPS EVO DSP PLUS TT 10.0-15.0-20.0-30.0 pf. 0,9
10.0
15.0
10 KVA
15 KVA
9 KW
13,5 KW
On-Line Double Conversion Transformerless (VFI-SS-111)
250 x 815 x 826
360 / 380 / 400 / 415 Vac (selectable)
208 / 220 / 230 / 240 Vac (selectable)
110 Vac ± 3% (Phase-Neutral) at 50% Load
176 Vac ± 3% (Phase-Neutral) at 100% Load
300 Vac ± 3% (Phase-Neutral)
360 / 380 / 400 / 415 Vac (selectable)
208 / 220 / 230 / 240 Vac (selectable)
±1% (Normal mode and Battery mode; at 100% Linear Load)
(50 Hz ± 0.1%) or (60 Hz ± 0.1%)
< 3% (100% Linear Load); < 5% (100% Non-Linear Load)
(100÷110)% for 10 min; (110÷130)% for 1 min; > 130% 1 sec
(100÷110)% for 30 sec; (110÷130)% for 10 sec; > 130% 1 sec
360 / 380 / 400 / 415 Vac (selectable)
208 / 220 / 230 / 240 Vac (selectable)
Lower Limit: 110÷209 Vac (selectable); upper Limit: 231÷276 Vac (selectable)
Lower Limit: 46÷49 Hz (selectable); upper Limit: 51÷54 Hz (selectable
Lower Limit: 56÷59 Hz (selectable); upper Limit: 61÷64 Hz (selectable
29
20.0
20 KVA
18 KW
0.9
3 Phases + Neutral
50/60 Hz (selectable)
± 7%
± 4%
0.99 (at 100% Load)
3 Phases + Neutral
True Sinewave
50/60 Hz (selectable)
3:1 max
0 ms
0 ms
< 10 ms
3 Phases + Neutral
ENGLISH
30.0
30 KVA
27 KW
300 x 1000 x 826