Uninterruptible Power Supply
EVO DSP PLUS MM 1.0 - pf 0,9
EVO DSP PLUS MM 2.0 - pf 0,9
EVO DSP PLUS MM 3.0 - pf 0,9
User's manual
Manuale utente

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EVO DSP PLUS MM 2.0 - pf 0,9 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tecnoware EVO DSP PLUS MM 2.0 - pf 0,9

  • Page 1 Uninterruptible Power Supply EVO DSP PLUS MM 1.0 - pf 0,9 EVO DSP PLUS MM 2.0 - pf 0,9 EVO DSP PLUS MM 3.0 - pf 0,9 User’s manual Manuale utente...
  • Page 3: Table Of Contents

    © Copyright 2018 TECNOWARE s.r.l. All rights reserved. All trademarks are property of their respective owners. TECNOWARE s.r.l. Via Montetrini, 2E – Molino del Piano – Florence – Italy www.tecnoware.com This manual has been printed and edited by TECNOWARE s.r.l. - November 2018 Edition – Version 1.0...
  • Page 4 Indice Manuale Utente – Italiano ..............24 Avvisi di Sicurezza ................24 1 Introduzione ................25 2 Caratteristiche Generali ..............26 3 Ricevimento e Collocazione ............. 26 4 Modi di Funzionamento ..............27 Modo NORMALE ............... 28 Modo BATTERIA ..............28 Modo BYPASS .................
  • Page 5: User's Manual - English

    User’s Manual - English Safety Warnings Read this manual carefully and completely before installing and using the TECNOWARE EVO DSP PLUS MM Uninterruptible Power Supply, which, from here after, will also be referred to as UPS. The UPS must be used only by properly trained personnel. To ensure correct and safe operations, it is necessary that operators and maintenance personnel observe the general safety Standards as well as the specific instructions included in this manual.
  • Page 6: Introduction

    ENGLISH 1 Introduction The UPS EVO DSP PLUS MM (UPS means Uninterruptible Power Supply) is the result of constant technological research aimed at obtaining the best performance at the lowest cost. EVO DSP PLUS MM is an advanced ON-LINE UPS built specifically to protect your computer from any irregularities in the AC line (for example blackouts, brownouts, over voltages, micro-interruptions), which often cause damage to hardware and software.
  • Page 7: General Characteristics

    ENGLISH 2 General Characteristics EVO DSP PLUS MM has all the advanced features which guarantee maximum reliability and safety: Double-Conversion ON-LINE Transformerless technology • Sinusoidal wave generated by an IGBT Inverter • Output Voltage regulation ±2% • Protection from overload and short circuits •...
  • Page 8: Operating Modes

    ENGLISH In all circumstances, see the “Technical Characteristics” chapter for environmental specifications and • check that the selected area meets these criteria. During normal operation the UPS discharges a minimal amount of heat. So it is necessary to leave at least •...
  • Page 9: Normal Mode

    ENGLISH 4.1 NORMAL Mode The UPS typically works in Normal mode: Input mains power is available and its amplitude is within specifications. Please refer to figure 1. After the filter has eliminated any high Frequency interference present on the mains, the AC Input line is rectified and conditioned in the Rectifier block (AC/DC conversion);...
  • Page 10: Stand-By Mode

    ENGLISH The Bypass mode is identified by: The graphic LCD panel shows the path of energy flow • during Bypass mode. An acoustic signal every 10 seconds. • During Bypass mode, loads are fed directly from AC Input line. Therefore some protections against AC Input line disturbances or interruptions is present.
  • Page 11: External Description

    ENGLISH 5 EXTERNAL DESCRIPTION 5.1 Front Panel The front panel informs the user about operating status, alarm conditions and measurements. It also provides access to controls and configuration parameters. Front panel shown below consists of two parts: Graphic LCD panel provides complete information about the energy flow path and existing alarms, Load and Battery level, Input, Output and Battery measurements.
  • Page 12: Graphic Lcd Panel

    ENGLISH 5.1.1 Graphic LCD Panel Please refer to figure 3. Backup Time Output Input & Battery Fault Info Buzzer Info Info Voltage Info Voltage Info Battery Load Info Info Mode Operation Programmable Info Output Info Figure 3 – Graphic LCD Panel User’s manual UPS EVO DSP PLUS MM...
  • Page 13 ENGLISH Graphic LCD Panel Function Backup time information Indicates how much time has passed in Battery mode. H: hours, M: minutes, S: seconds Fault information Indicates the warning that a fault has occurred. Indicates the Fault codes, and the codes are listed in the “Fault Table” of chapter Mute operation Indicates that the UPS alarm is disabled (muted).
  • Page 14: Buttons

    ENGLISH Graphic LCD Panel Function Battery information Indicates the Battery capacity by 0-25%, 26-50%, 51-75%, and 76-100%. Indicates the Battery is faulty or defective. Indicates Low Battery level and Low Battery Voltage. Input and Battery Voltage information Indicates the Input Voltage or Frequency or Battery Voltage. Vac: Input Voltage, Vdc: Battery Voltage, Hz: Input Frequency 5.1.2 Buttons Functions of the buttons are given below:...
  • Page 15: Acoustic Alarm

    ENGLISH 5.1.3 Acoustic Alarm UPS status Acoustic Alarm Battery Mode Beeping once every 4 seconds Low Battery Beeping once every second Overload Beeping twice every second Fault Mode Beeping continuously Bypass Mode Beeping once every 10 seconds Note: OFF = YES : means that the buzzer can be muted or stopped, by pressing ON/MUTE button. : means that the buzzer can NOT be muted or stopped OFF = NO 5.2 Rear Side...
  • Page 16: Electrical Installation

    For the Input/Output connections use ONLY the included power cables or cables with the same power ratings. TECNOWARE declines any responsibility if this warning is disregarded. The EVO DSP PLUS MM models are made of a single unit design that contains the electronic parts and batteries.
  • Page 17: First Start Up

    There are no internal parts in the UPS which are user serviceable. Any repair or maintenance work must be performed exclusively by qualified technical personnel authorized by TECNOWARE. TECNOWARE declines any responsibility if this warning is disregarded. Disregard for these warnings may lead to a risk of electric shock to operators.
  • Page 18: Functioning

    ENGLISH 8 Functioning 8.1 Turning ON and OFF Let’s see carefully the consequences of the pressure of ON/MUTE and OFF buttons. The UPS is in Stand-by mode (the Inverter is OFF); if the ON/MUTE button is pressed, after few seconds the Inverter starts and the UPS switches in Normal mode.
  • Page 19: Load Testing

    ENGLISH 8.3 Load Testing The UPS indicates the Output Load level by graphic LCD (on the right side as described in the chapter 5). When the Output load is higher than nominal value the UPS warns of Overload condition by graphic LCD and by acoustic alarm as described in the “Warning Table”...
  • Page 20: Battery Test

    ENGLISH 8.5 Battery Test It is possible to check the Battery Status when the UPS is running in Normal mode, by performing a Battery Test. To perform the Battery Test, press the ON/MUTE button continuously for at least 5 seconds. The Battery Test starts immediately and it finishes after some seconds.
  • Page 21: Operation In Fault Mode

    The RS-232 and USB signals are all isolated through photo-couplers from the dangerous voltages that are present inside the UPS. Connecting to the Web site www.tecnoware.com, it is possible to download, free of charge, the update UPS management Software, compatible with the most popular Operative Systems.
  • Page 22: Technical Characteristics

    ENGLISH 10 Technical Characteristics UPS EVO DSP PLUS MM Model Power 1000 VA 2000 VA 3000 VA Nominal Active Power 900 W 1800 W 2700 W Power Factor Technology On-Line Double Conversion Transformerless Dimension (W x H x D) 14,5 x 22 x 28,2 cm 14,5 x 22 x 39,7 cm 19 x 31,8 x 42,1 cm Net Weight...
  • Page 23 ENGLISH ENVIRONMENTAL CONDITIONS Storage Temperature Range -25°C to +55°C (15°C to 40°C recommended for longer Battery life) Operating Temperature Range 0°C to +40°C (20°C to 25°C recommended for longer Battery life) Relative Humidity Range 0% - 95% (non condensing) Max. Altitude without Derating 3000 m Protection level IP 20...
  • Page 24: Maintenance

    ENGLISH 11 Maintenance 11.1 UPS Cleaning Before starting any cleaning operation, be sure that: 1. The AC Input Voltage for the UPS has been removed. 2. The UPS is completely OFF (the graphic LCD panel is OFF). Use only a cloth dampened with water to clean the unit. If UPS works in an environmental unusually dusty or dirty, remove the dirty from the ventilation holes.
  • Page 25: Troubleshooting

    There are no internal parts in the UPS which are user serviceable. Any repair or maintenance work must be performed exclusively by qualified technical personnel authorized by TECNOWARE. TECNOWARE declines any responsibility if this warning is disregarded. SYMPTOM POSSIBLE CAUSE...
  • Page 26 Technical Service. flash on LCD display and alarm beeps every second. If the described anomalies should continue despite the advised troubleshooting, or should they manifest in any other form, please contact: TECNOWARE SERVICE www.tecnoware.com User’s manual UPS EVO DSP PLUS MM...
  • Page 27: Conformity To The European Directives

    ENGLISH Conformity to the European Directives TECNOWARE S.r.l. confirms that EVO DSP PLUS MM models comply with the requirements set out in: the Low Voltage (Safety) Directive 2014/35/EU and following amendments, the EMC (Electro-Magnetic Compatibility) Directive 2014/30/EU and following amendments.
  • Page 28: Manuale Utente - Italiano

    Avvisi di Sicurezza Leggere attentamente e completamente questo manuale prima di installare ed utilizzare il gruppo di continuità TECNOWARE della serie EVO DSP PLUS MM, che in seguito verrà chiamato anche semplicemente UPS. L'UPS deve essere utilizzato solo da personale opportunamente istruito. Per l’uso corretto e in condizioni di sicurezza è...
  • Page 29: Introduzione

    ITALIANO 1 Introduzione L’UPS EVO DSP PLUS MM (UPS significa Uninterruptible Power Supply) è il risultato di una costante ricerca tecnologica mirata all'ottenimento delle migliori prestazioni a costi estremamente contenuti. EVO DSP PLUS MM è un gruppo di continuità monofase ad onda sinusoidale progettato per alimentare e proteggere le più...
  • Page 30: Caratteristiche Generali

    ITALIANO 2 Caratteristiche Generali EVO DSP PLUS MM presenta tutte le moderne caratteristiche che garantiscono massima affidabilità e sicurezza: Tecnologia ON-LINE doppia conversione senza trasformatore • Onda sinusoidale generata tramite Inverter ad IGBT • Stabilizzazione in Uscita ± 2% • Protezione dal sovraccarico e dal cortocircuito •...
  • Page 31: Modi Di Funzionamento

    ITALIANO Consultare comunque il capitolo “Caratteristiche Tecniche” per i requisiti ambientali e controllare che il • luogo scelto rientri in tali specifiche. Durante il normale funzionamento l’UPS emette una quantità minima di calore. È perciò necessario • lasciare uno spazio libero di almeno 10 cm sia lateralmente che sul retro dell’UPS per permetterne una sufficiente areazione.
  • Page 32: Modo Normale

    ITALIANO 4.1 Modo NORMALE È il modo tipico di funzionamento. In questo caso la Tensione di Rete elettrica è presente in Ingresso ed ha ampiezza all'interno delle specifiche. Fare riferimento alla figura 1. La Tensione d’Ingresso, dopo che il filtro ha eliminato eventuali disturbi in alta frequenza presenti sulla Rete elettrica, viene raddrizzata e condizionata nel blocco Raddrizzatore (conversione CA/CC);...
  • Page 33: Modo Stand-By

    ITALIANO Il modo Bypass è caratterizzato da: Il display grafico LDC mostra il percorso del flusso di • energia durante il modo Bypass. Emissione di un breve segnale acustico ogni 10 secondi. • In modo Bypass, i carichi sono alimentati direttamente dalla linea elettrica d’Ingresso tramite il Bypass.
  • Page 34: Descrizione Esterna

    ITALIANO 5 Descrizione Esterna 5.1 Pannello Frontale Il pannello frontale informa l’utente sullo stato di funzionamento, sulle condizioni di allarme e sulle misure. Inoltre consente di controllare e configurare i parametri di funzionamento. Il pannello frontale, mostrato nella figura 2, è costituito da 2 parti: Un pannello LCD grafico che fornisce le informazioni complete sul percorso del flusso energia per i vari modi di funzionamento, sugli allarmi esistenti, sul carico in Uscita, sulle batterie, e sulle misure delle grandezze elettriche della linea d’Ingresso, d’Uscita e delle batterie.
  • Page 35: Pannello Lcd Grafico

    ITALIANO 5.1.1 Pannello LCD Grafico Prego riferirsi alla figura 3. Info Allarme Info Info Tensione Info Info Fault Acustico Tempo Backup d’Ingresso e di Batteria Tensione d’Uscita Info Info Batteria Load Info Modo di Info Output Funzionamento Programmabile Figura 3 – Pannello LCD grafico UPS EVO DSP PLUS MM Manuale utente...
  • Page 36 ITALIANO Pannello LCD Grafico Funzione Informazioni del Tempo di Backup Indica quanto tempo è trascorso in modo Batteria. H: ore, M: minuti, S: secondi Informazioni di Guasto (Fault) Indica che si è verificata una situazione di Allarme o di Guasto (Fault). Indica il codice di Fault: la lista dei codici è...
  • Page 37: Pulsanti

    ITALIANO Pannello LCD Grafico Funzione Informazione della Batteria Indica che la capacità della Batteria è compresa tra 0-25%, 26-50%, 51-75% e 76-100%. Indica che la Batteria è guasta Indica la condizione di Batteria scarica (Low Battery) e quindi di bassa Tensione Batteria.
  • Page 38: Allarme Acustico

    ITALIANO 5.1.3 Allarme Acustico Stato UPS Allarme acustico Modo Batteria Allarme acustico ogni 4 secondi Low Battery (Fine Autonomia) Allarme acustico ogni secondo Overload Allarme acustico 2 volte ogni secondo Condizioni di Guasto (Fault) Allarme acustico continuo Modo Bypass Allarme acustico ogni 10 secondi Nota: OFF = SI : indica che l’allarme acustico può...
  • Page 39: Installazione Elettrica

    Per i collegamenti d’Ingresso/Uscita utilizzare esclusivamente i cavi in dotazione con il prodotto o cavi con analoghe caratteristiche. In caso contrario TECNOWARE declina ogni sua responsabilità. I modelli EVO DSP PLUS MM sono costituiti da un’unità singola che contiene sia l’elettronica che le batterie.
  • Page 40: Prima Accensione

    L’UPS non ha parti interne soggette a manutenzione da parte dell’utente. Interventi tecnici di qualsiasi tipo devono essere compiuti solo da personale tecnico specializzato ed autorizzato da TECNOWARE. In caso contrario TECNOWARE declina ogni sua responsabilità. Non rispettare queste precauzioni espone l'operatore al pericolo di shock elettrico.
  • Page 41: Funzionamento

    ITALIANO 8 Funzionamento 8.1 Accensione e Spegnimento Vediamo con attenzione le conseguenze della pressione dei pulsanti ON/MUTE e OFF. L’UPS è in modo Stand-By (Inverter disattivo): se viene premuto il pulsante ON/MUTE, dopo alcuni secondi l'UPS attiva l'Inverter e commuta nel modo Normale. L’UPS è...
  • Page 42: Controllo Del Carico

    ITALIANO 8.3 Controllo del Carico L’UPS indica il livello del carico in Uscita per mezzo del display grafico, visualizzandolo a destra, come descritto nel capitolo 5. Quando il carico in Uscita supera il valore nominale l’UPS segnala la condizione di Overload (Sovraccarico) per mezzo del display grafico e dell’allarme acustico, come descritto nella “Tabella Allarmi”...
  • Page 43: Test Batteria

    ITALIANO 8.5 Test Batteria Per controllare lo stato delle batterie è possibile svolgere un Test Batteria durante il funzionamento in modo Normale. Per svolgere il Test Batteria è sufficiente premere il pulsante ON/MUTE del pannello frontale continuativamente per almeno 5 secondi: il test si avvia immediatamente e si conclude dopo alcuni secondi. Se il test è superato, l’UPS non segnala nessun allarme.
  • Page 44: Segnalazioni Di Guasto

    I segnali delle Interfacce RS-232 e USB sono tutti isolati tramite foto-accoppiatori dalle tensioni pericolose presenti all’interno dell’UPS. Collegandosi al sito internet www.tecnoware.com è possibile scaricare gratuitamente la versione aggiornata del software di gestione dell’UPS, compatibile con i più diffusi Sistemi Operativi.
  • Page 45: Caratteristiche Tecniche

    ITALIANO 10 Caratteristiche Tecniche Modello UPS EVO DSP PLUS MM Potenza 1000 VA 2000 VA 3000 VA Potenza Attiva Nominale 900 W 1800 W 2700 W Fattore di Potenza Tecnologia On-Line Doppia Conversione senza Trasformatore Dimensioni (L x H x P) 14,5 x 22 x 28,2 cm 14,5 x 22 x 39,7 cm 19 x 31,8 x 42,1 cm...
  • Page 46 ITALIANO CARATTERISTICHE AMBIENTALI da -25°C a +55°C Range Temperatura Immagazzinamento (si consiglia da 15°C a 40°C per avere una più lunga vita delle batterie) da 0°C a +40°C Range Temperatura Funzionamento (si consiglia da 20°C a 25°C per avere una più lunga vita delle batterie) Range Umidità...
  • Page 47: Manutenzione

    ITALIANO 11 Manutenzione 11.1 Pulizia dell’UPS Prima di avviare la procedura d'installazione, accertarsi che: 1. La linea elettrica d’Ingresso all’UPS sia scollegata. 2. L’UPS sia completamente spento (solo in tal caso il display LCD grafico è spento). Pulire le superfici esterne usando un panno leggermente inumidito solo con acqua. Se l’UPS opera in un ambiente insolitamente polveroso o sporco, rimuovere la polvere dalle feritoie.
  • Page 48: Anomalie Ed Interventi

    L’UPS non ha parti interne soggette a manutenzione da parte dell’utente. Interventi tecnici di qualsiasi tipo devono essere compiuti solo da personale tecnico specializzato ed autorizzato da TECNOWARE. In caso contrario TECNOWARE declina ogni sua responsabilità. ANOMALIA POSSIBILE CAUSA AZIONI PER RISOLVERE Controllare accuratamente il Il cavo della linea d’Ingresso Rete...
  • Page 49 Servizio Assistenza. interna dell’UPS è troppo alta. e l’allarme acustico suona ogni secondo. Se le anomalie descritte permanessero nonostante gli interventi consigliati, o si manifestassero problemi di altra natura, contattare: TECNOWARE SERVICE www.tecnoware.com UPS EVO DSP PLUS MM Manuale utente...
  • Page 50: Conformità Alle Direttive Europee

    ITALIANO Conformità alle Direttive Europee TECNOWARE S.r.l. dichiara che i prodotti EVO DSP PLUS MM sono conformi ai requisiti stabiliti nella Direttiva Bassa Tensione (Sicurezza) 2014/35/UE e successive modifiche, e nella Direttiva EMC (Compatibilità Elettromagnetica) 2014/30/UE e successive modifiche. Attenzione – EVO DSP PLUS MM è un UPS di categoria C2. Quando utilizzato in ambienti residenziali, questo prodotto può...
  • Page 52 TECNOWARE s.r.l. www.tecnoware.com...

Table of Contents