Brake Chopper

9.1.3 Parameter Setting Description

b0.10: Parameter initialization
Code
b0.10
Parameter initialization
0: Inactive
This parameter will be reset to '0: Inactive' automatically after parameter initi-
alization.
1: Restore to default settings
All parameters are restored to factory default settings except for:
H6.50, H6.51, H6.52, H6.53, H6.54, H6.55 (error records).
2: Clear error record
Parameter H6.50, H6.51, H6.52, H6.53, H6.54, H6.55 (error records) will be
cleared.
b0.11: Parameter copy
This function is used for the same settings of multiple brake choppers via the
operating panel.
With this function, users only need set parameters of one brake chopper, and
then replicate its settings for all the other brake choppers.
Code
b0.11
Parameter copy
0: Inactive
This parameter will be reset to '0: Inactive' automatically after parameter rep-
lication.
1: Backup parameters to panel (from source brake chopper to panel)
All parameter settings are copied from the source brake chopper to the ope-
rating panel EXCEPT that of
– Read-only parameters
– H6.50, H6.51, H6.52, H6.53, H6.54, H6.55 (error records)
– b0.10, b0.11, b0.20
2: Restore parameters from panel (from panel to target brake choppers)
All parameter settings are replicated from the operating panel to the target
brake choppers EXCEPT that of
– Read-only parameters
– H6.50, H6.51, H6.52, H6.53, H6.54, H6.55 (error records)
– b0.10, b0.11, b0.20